![Mitsubishi SRK100VNXWPZSX Скачать руководство пользователя страница 123](http://html1.mh-extra.com/html/mitsubishi/srk100vnxwpzsx/srk100vnxwpzsx_service-manual_1808154123.webp)
-
122
-
'20 • PAC-SM-351
E49
1. Applicable model
5. Troubleshooting
Diagnosis
Countermeasure
NO
YES
NO
YES
Is the
service valve fully
opened?
Are the
connections of low
pressure sensor and suction pipe
temprerature sensor
connector OK?
NO
YES
NO
YES
Are the
characteristics of
low pressure sensor, suction
pipe temperature
sensor OK?
Is the low
pressure normal during
operation?
From previous page
Open fully.
Correct connector.
Defective low pressure
sensor, suction
pipe temperature
sensor
➞
Replace.
Charge refrigerant.
Defective outdoor unit
control PCB
➞
Replace.
(Defective low pressure
sensor, suction pipe
temperature sensor circuits)
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
Note:
Error code
Remote control:
LED
Green
Red
Outdoor control PCB
Outdoor inverter
PCB
1-time flash
Keeps flashing
Indoor control PCB
Stays OFF
Keeps flashing
Content
Keeps flashing
Yellow LED
Low pressure error or
low pressure sensor anomaly (2/2)
Содержание SRK100VNXWPZSX
Страница 2: ...1 20 PAC SM 351 TABLE OF CONTENTS 1 HYPER INVERTER PACKAGED AIR CONDITIONERS 2 2 V MULTI SYSTEM 199...
Страница 181: ...180 20 PAC SM 351 1 e SRK series PHA012D402...
Страница 182: ...181 20 PAC SM 351 Screw...
Страница 183: ...182 20 PAC SM 351 3 PHA012D402...
Страница 184: ...183 20 PAC SM 351 4 PHA012D402...