141
-
'20 • PAC-SM-351
WAIT
Communication error at
initial operation (1/3)
–
–
Keeps flashing 2-time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
NO
NO
“ ” is still displayed on the
remote control LED 2 minutes after
power ON.
YES
NO
Is the outdoor
unit control green LED
flashing?
YES
Is the outdoor unit
control red LED flashing
twice?
Are wires
connected properly between indoor/
outdoor units?
YES
YES
YES
YES
NO
Is approx.
DC20V detected between
➁
-
➂
on
the outdoor unit terminal
block?
Is approx.
DC20V detected between
➁
-
➂
on
the indoor unit terminal
block?
WA IT
To next page
Defective indoor unit control PCB
➞
Replace.
Defective remote control
➞
Replace.
Broken remote control wire X or Y
➞
Replace.
Correct connection wires
between indoor and
outdoor units.
Defective outdoor unit
control PCB
➞
Replace.
Defective connection wire
(Broken)
Noise
Defective indoor unit control
PCB
➞
Replace.
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
• Faulty indoor unit control PCB
• Defective remote control
• Broken remote control wire
• Faulty outdoor unit control PCB
• Broken connection wires
Note:
Error code
Remote control:
Indoor
display
RUN light TIMER light
Green LED Red LED
Outdoor unit
control PCB
Content