129
-
'20 • PAC-SM-351
Error code
Remote control:
Indoor
display
RUN light TIMER light
Green LED Red LED
Outdoor unit
control PCB
Content
(b) SRK series
None
Operates but does not cool
–
–
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
temperature difference
between return and supply air
10-20◦C at
cooling?
Check the indoor unit fan operation.
Check the temperature difference
between return and supply air.
Does the
heat load increase after
installation?
“ ”
message is displayed (for 3 seconds) when
performing cooling, defrost and heating
operations from the remote
control.
Is the
compressor rotation
speed low?
Are the
temperature conditions
of room and outdoor air close
to the rated
conditions?
Mistake in model selection.
Calculate heat load once more.
Check which control “Determination
control of compressor rotation speed” or
“Protective control by controlling
compressor rotation speed” is appropriate
to this phenomenon.
The unit is operating normally but is
operating under the contol for protecting
compressor or other respective parts.
NO
YES
YES
NO
YES
YES
YES
NO
NO
Is the compressor
operating?
NO
YES
NO
Note (1) Outdoor: 35°C, Indoor: 27°C
(1)
WAIT
It is normal.
(This unit is designed to
start in the soft start mode
by detecting the under dome
temperature of compressor
when it restart after power
reset.
It is necessary to replace to
higher capacity one or two
install additional unit.
Compressor refrigerant oil
protection control at starting
is activated. For the contents
of control, refer to the
compressor start control of
the microcomputer control
functions.
Compressor may be stopped
by the error detection
control. For the contents of
control, refer to anomalous
stop control by controlling
compressor rotation speed
of microcomputor control
functions.
Inspect the followings.
• Minor clogging of filter
• Minor clogging of heat
exchanger
• Minor short-circuit
• Minor shortage of
refrigerant amount
• Poor compression of
compressor
Considering appropriate
operation control, check
suspicious points.
Inspect the followings for
reference.
• Major clogging of filter
• Major clogging of heat
exchanger
• Major short-circuit
• Major shortage of
refrigerant amount
•
Compressor protection ON
• Indoor fan tap
• Valid setting of silent mode
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
•
Poor compression of
compressor
•
Faulty expansion valve
operation
Note: