'20 • PAC-SM-351
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
None
Louver motor failure
Keeps flashing
Stays OFF
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
FDT, FDTC, FDE series
Diagnosis
Countermeasure
NO
YES
Is LM wiring
broken?
Is LM locked?
▲ Check at the indoor unit side.
LM: louver motor
Is the louver
operable with the remote
control?
YES
NO
Does the louver
operate at the power
on?
YES
NO
YES
NO
Operate after
waiting for more
than 1 minute.
Repair wiring.
Defective indoor unit
control PCB
➞
Replace.
Replace LM.
Normal
Adjust LM lever and then
check again.
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
• Defective LM
• LM wire breakage
• Faulty indoor unit control
PCB