5 - 15
5.4 Precautions for Wiring/Connecting the EMC Directive-Compliant Product
5.4.2
Processing connection cables
Process the cable used with the GOT with the following method.
When processing the cable, ferrite core, cable clamp and shielding material are required.
The cable clamp used by Mitsubishi Electric for the EMC specification compatibility test is shown below.
• TDK corporation brand ZCAT3035-1330 Ferrite Core
• Mitsubishi Electric Model AD75CK cable clamp
• Japan Zipper Tubing Co., Ltd. Zipper tube SHNJ type
(1) BUS connection cable
(a) For GT15-QC
B, GT15-QC
BS
• Peel the sheath (with the length shown below) at both ends of the cable, and expose the shield braided
wire for grounding. (For grounding with cable clamps. (refer to Section 5.4.3.))
(b) For GT15-C
BS
• Cut the connection wire protruding from both ends of the cable to the lengths shown below.
• Attach the ferrite core to the cable in the position as illustrated below and insert the ground wire into the
ferrite core.
• Peel the sheath (with the length shown below) at both ends of the cable, and expose the shield braided
wire for grounding. (For grounding with cable clamps. (refer to Section 5.4.3.))
Unit : mm (inch)
360 or less
(14.17)
360 or less
(14.17)
(1.57)
(1.57)
40
40
GOT side
PLC/GOT side
60 or less
GOT side
PLC/GOT side
Ferrite Core
(ZCAT3035-1330)
360 or less
(2.36)
(14.17)
(1.57)
40
60 or less
360 or less
(2.36)
(14.17)
(1.57)
40
Unit : mm (inch)
Ground wires
(280mm
(11.02 inch))
Содержание GOT 1000 GT16
Страница 1: ...GT16 User s Manual Hardware ...
Страница 2: ......
Страница 14: ...A 12 INDEX REVISIONS WARRANTY ...
Страница 193: ...10 3 Error Message and System Alarm 10 29 9 MAINTENANCE AND INSPECTION 10 TROUBLESHOOTING APPENDICES ...
Страница 210: ...App 17 ...
Страница 212: ...Index 2 Transportation Precautions App 15 U USB environmental protection cover 2 17 8 19 ...
Страница 217: ......