10.1 GOT Restoration Sheet
10 - 5
9
M
A
IN
TE
N
A
N
C
E AN
D
IN
SP
ECTIO
N
10
TROU
BLES
H
OOTING
APP
ENDICES
(4) GOT restoration procedure
Follow the procedures below starting from (a) and in order to check if the GOT is restored.
If the GOT is not restored, proceed to the next item.
*1 The GOT reset switch does not operate when the bus connection is used.
*2 When the bus connection is used, do not power the GOT ON again (OFF
ON) while the power of the PLC is ON.
When powering the GOT ON again (OFF
ON), power OFF the PLC before that.
*3 By powering OFF the GOT, an error occurs in the control station when the MELSECNET/H connection is used or in the master
station when the CC-Link connection (intelligent device station) is used.
(5) Troubled product investigation
When malfunction of the GOT is not improved, please contact your local Mitsubishi (Electric System) Service.
Depending on the problem details, we may ask you to return the troubled product to us.
In that case, please attach the GOT status check sheet, GOT installation status check sheet, and the system
configuration check sheet filled out with details of your system.
Check item
Cause
Action
(a) Press the GOT reset switch.
*1, 3
Restored Not restored
(Proceed to (b).)
The GOT may have malfunctioned
temporarily due to noise.
Take the action of (4)-(h).
(b) Power the GOT ON/OFF.
*2, 3
Restored Not restored
(Proceed to (c).)
(c) Reset or power ON/OFF the PLC
CPU.
Restored Not restored
(Proceed to (d).)
(d) Power the GOT and PLC CPU ON/
OFF simultaneously.
Restored Not restored
(Proceed to (e).)
(e) Connect the cable again.
Restored Not restored
(Proceed to (f).)
The cable connection may be faulty.
Securely connect the cable.
If an error occurs again, proceed to (5)
Troubled product investigation.
(f) Reinstall the project data.
Restored Not restored
(Proceed to (g).)
Data may have been destroyed by an
action such as powering the GOT OFF
during the installation of project data or
OS.
Do not power the GOT OFF while
transferring data.
If an error occurs again, proceed to (5)
Troubled product investigation.
(g) Reinstall the OS.
Restored Not restored
(Proceed to (h).)
(h) Take the action described in the
"Action" column.
Restored Not restored
(Proceed to (i).)
The GOT may have malfunctioned
temporarily due to noise.
Take the action with referring to
installation status check sheet.
(i) Replace the unit/module.
Restored Not restored
The hardware of the unit/module may be
faulty.
Install the unit/module with which the
GOT malfunctioned again to see if the
unit/module caused the malfunction.
After checking, proceed to (5) Troubled
product investigation.
The GOT is not restored even by
performing (a) to (i).
Proceed to (5) Troubled product
investigation.
Содержание GOT 1000 GT16
Страница 1: ...GT16 User s Manual Hardware ...
Страница 2: ......
Страница 14: ...A 12 INDEX REVISIONS WARRANTY ...
Страница 193: ...10 3 Error Message and System Alarm 10 29 9 MAINTENANCE AND INSPECTION 10 TROUBLESHOOTING APPENDICES ...
Страница 210: ...App 17 ...
Страница 212: ...Index 2 Transportation Precautions App 15 U USB environmental protection cover 2 17 8 19 ...
Страница 217: ......