7.4 Panel Inside Wiring, Panel Outside Wiring
7.4 Panel Inside Wiring, Panel Outside Wiring
7.4.1
Panel inside wiring
In wiring, the power line connected to the power or servo amplifier and the communication cable such as bus connection
cable or network cable must not be mixed.
Mixing the power line and communication cable may cause malfunction due to noise.
When using an equipment that may occur surge noise, such as molded case circuit breaker (MCCB), electromagnetic
contactor (MC), relay (RA), solenoid valve, or induction motor, using a surge suppressor is effective.
For surge suppressor, refer to the following.
7.5 Attaching Surge Suppressor for Control Equipment
7.4.2
Panel outside wiring
When leading the power line and communication cable outside the panel, open cable holes at two separate places to
lead the cables separately out.
If cables are led out through the same cable hole for wiring reasons, the cables are more easily influenced by noise.
Install the power line and communication cable as apart from each other as possible in the duct.
If the cables are installed closely with each other for wiring reasons, using a separator (made of metal) can make the
cables less influenced by noise.
Wiring for leading the power line and communication cable out from the panel
Wiring of power lines and communication cables in the duct
PLC's I/O wire
PLC's I/O wire
NFB
MC
MC
RA
RA
NFB
MC
MC
RA
RA
Separated power lines and communication cables
Mixed power lines and communication cables
Power cable
Power cable
Control panel inside
Control panel inside
GOT
connection
cable
GOT
connection
cable
Drive control
wire
Drive control
wire
Terminal block
Terminal block
Communication
cable
Communication
cable
Power line
Power line
Cable hole
100mm or more
Power line
Wiring duct
Power line
Signal line
Communication cable
Separator
Содержание GOT 1000 GT16
Страница 1: ...GT16 User s Manual Hardware ...
Страница 2: ......
Страница 14: ...A 12 INDEX REVISIONS WARRANTY ...
Страница 193: ...10 3 Error Message and System Alarm 10 29 9 MAINTENANCE AND INSPECTION 10 TROUBLESHOOTING APPENDICES ...
Страница 210: ...App 17 ...
Страница 212: ...Index 2 Transportation Precautions App 15 U USB environmental protection cover 2 17 8 19 ...
Страница 217: ......