A953 HANDY GOT
Connection to PLC by Sharp 11
11-5
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
11.4
Connection cable
The connection diagram and the connector of RS-232C cables which connect the PLC CPU
and the GOT are shown below.
1) Connection diagram
a) PLC CPU (JW-22CU, JW-70CUH or JW-100CUH)
b) PLC CPU (JW-32CUH or JW-33CUH)
GOT side (F9GT-HCAB
-3M)
(
= none or 1)
Cable connection and signal direction
Sharp PLC side
(15-pin D-Sub,
male, milli-thread
type)
Signal
name
Untied
wire color
Pin
number
Pin
number
Signal
name
CD(DCD)
Blue
8
1
FG
RD(RXD)
Red
4
2
SD(TXD)
SD(TXD)
Black
2
3
RD(RXD)
ER(DTR)
White
3
4
RS(RTS)
SG(GND)
Orange
10
5
CS(CTS)
DR(DSR)
Green
5
7
SG(GND)
RS(RTS)
Yellow
6
12
CS(CTS)
Brown
7
14
FG
(SHIELD)
Drain wire
1
GOT side (F9GT-HCAB
-3M)
(
= none or 1)
Cable connection and signal direction
Sharp PLC side
(15-pin D-Sub,
male, milli-thread
type)
Signal
name
Untied
wire color
Pin
number
Pin
number
Signal
name
CD(DCD)
Blue
8
FG
1
RD(RXD)
Red
4
SD(TXD)
2
SD(TXD)
Black
2
RD(RXD)
4
ER(DTR)
White
3
RS(RTS)
8
SG(GND)
Orange
10
CS(CTS)
12
DR(DSR)
Green
5
SG(GND)
7
RS(RTS)
Yellow
6
CS(CTS)
Brown
7
FG
(SHIELD)
Drain wire
1
Class D grounding
Class D grounding
Содержание A953GOT-LBD-M3-H
Страница 1: ...HARDWARE MANUAL A953 HANDY GOT TARGET MODELS FOR RS 232C CONNECTION A953GOT LBD M3 H A953GOT SBD M3 H ...
Страница 4: ...A953 HANDY GOT ii ...
Страница 6: ...A953 HANDY GOT iv ...
Страница 14: ...A953 HANDY GOT xii MEMO ...
Страница 28: ...A953 HANDY GOT Introduction 1 1 8 MEMO ...
Страница 42: ...A953 HANDY GOT Installation Wiring 2 2 14 MEMO ...
Страница 58: ...A953 HANDY GOT Wiring and Handling of Switches 3 3 16 MEMO ...
Страница 72: ...A953 HANDY GOT Specifications 4 4 14 MEMO ...
Страница 80: ...A953 HANDY GOT CPU Direct Connection 6 6 6 MEMO ...
Страница 98: ...A953 HANDY GOT Connection to PLC by Omron 8 8 10 MEMO ...
Страница 104: ...A953 HANDY GOT Connection to PLC by Yaskawa Electric 9 9 6 MEMO ...
Страница 108: ...A953 HANDY GOT Connection to PLC by Allen Bradley 10 10 4 MEMO ...
Страница 130: ...A953 HANDY GOT Connection to PLC by Siemens 13 13 4 MEMO ...
Страница 134: ...A953 HANDY GOT Diagnostics 14 14 4 MEMO ...
Страница 141: ......