APP - 5
APPENDICES
Table 1.3 Setting data error (1 to 99) list (Continued)
Error
code
Erroneous
data
Check timing
Error cause
Error
processing
Corrective action
40
Parameter
block
Interpolation control
start
The interpolation control
unit of the parameter
block is different from
the control unit of the
fixed parameters.
Control with
the control
unit of the
fixed
parameters.
Set the same control unit
of the fixed parameters
and servo parameters.
POINT
When the interpolation control unit of parameter block is different from the control
unit of the fixed parameters, an error code may not be stored with the combination
of units.
Refer to Section 6.11.6 for details.