4
2. Installation location
2.1. Refrigerant pipe
Refer to Fig. 4-1.
2.2. Choosing the outdoor unit installation location
$YRLGORFDWLRQVH[SRVHGWRGLUHFWVXQOLJKWRURWKHUVRXUFHVRIKHDW
6HOHFW D ORFDWLRQ IURP ZKLFK QRLVH HPLWWHG E\ WKH XQLW ZLOO QRW LQFRQYHQLHQFH
neighbors.
6HOHFWDORFDWLRQSHUPLWWLQJHDV\ZLULQJDQGSLSHDFFHVVWRWKHSRZHUVRXUFHDQG
indoor unit.
$YRLGORFDWLRQVZKHUHFRPEXVWLEOHJDVHVPD\OHDNEHSURGXFHGÀRZRUDFFXPX
-
late.
1RWHWKDWZDWHUPD\GUDLQIURPWKHXQLWGXULQJRSHUDWLRQ
6HOHFWDOHYHOORFDWLRQWKDWFDQEHDUWKHZHLJKWDQGYLEUDWLRQRIWKHXQLW
$YRLG ORFDWLRQV ZKHUH WKH XQLW FDQ EH FRYHUHG E\ VQRZ ,Q DUHDV ZKHUH KHDY\
snow fall is anticipated, special precautions such as raising the installation location
or installing a hood on the air intake must be taken to prevent the snow from
EORFNLQJWKHDLULQWDNHRUEORZLQJGLUHFWO\DJDLQVWLW7KLVFDQUHGXFHWKHDLUÀRZDQG
a malfunction may result.
$YRLGORFDWLRQVH[SRVHGWRRLOVWHDPRUVXOIXULFJDV
8VHWKHWUDQVSRUWDWLRQKDQGOHVRIWKHRXWGRRUXQLWWRWUDQVSRUWWKHXQLW,IWKHXQLWLV
FDUULHGIURPWKHERWWRPKDQGVRU¿QJHUVPD\EHSLQFKHG
2.3. Outline dimensions (Outdoor unit) (Fig. 2-1)
2.4. Constraints on indoor unit installation
You should note that indoor units that can be connected to this outdoor unit have
the following constraints.
,QGRRUXQLWVZLWKPRGHOLQWDEOHFDQEHFRQQHFWHG
)RUWKHQXPEHURIXQLWVWKDWFDQEHFRQQHFWHGUHIHUWR7DEOHEHORZ
7KHWRWDOUDWHGFDSDFLW\FRROLQJRIWKHFRQQHFWHGLQGRRUVXQLWVUHIHUWR7DEOH
must not exceed 130% of the outdoor unit capacity (refer to the capacity range of
connected units in Table 1).
7DEOH1XPEHURIXQLWVWKDWFDQEHFRQQHFWHGDQGFDSDFLW\UDQJHRIFRQQHFWHGXQLWV
Outdoor unit
model name
The capacity of
outdoor unit
1XPEHURIXQLWVWKDW
can be connected
Capacity range of
connected units
380<31.08
36 kBtu/h
1 - 9 units
18 - 46.8 kBtu/h
380<+31.08
380<31.08
48 kBtu/h
1 - 12 units
24 - 62.4 kBtu/h
380<+31.08
380<31.08
60 kBtu/h
1 - 12 units
30 - 78.0 kBtu/h
Table 2: Rated capacity (cooling) of the indoor units
Indoor unit type P05 P06 P08 P12 P15 P18 P24 P30 P36 P48 P54 P72
Rated capacity
(Cooling)
(kBtu/h)
5
6
8
12
15
18
24
30
36
48
54
72
([DPSOH380<31.08
PEFY-P24 = 24
+
PEFY-P18 = 18
+
PEFY-P18 = 18
Combinations in which the total capacity of indoor units exceeds the capacity of the
outdoor unit will reduce the cooling capacity of each indoor unit below their rated
cooling capacity. Thus, combine indoor units with an outdoor unit within the outdoor
unit’s capacity, if possible.
9HQWLODWLRQDQGVHUYLFHVSDFH
Note:
The dimensions given along the arrows above are required to guarantee the
air conditioner’s performance. Install the unit in as wide a place as possible
for later service or repairs.
:LQG\ORFDWLRQLQVWDOODWLRQ
When installing the outdoor unit on a rooftop or other location unprotected from the
wind, situate the air outlet of the unit so that it is not directly exposed to strong winds.
6WURQJZLQGHQWHULQJWKHDLURXWOHWPD\LPSHGHWKHQRUPDODLUÀRZDQGDPDOIXQFWLRQ
may result.
The following shows three examples of precautions against strong winds.
1
Face the air outlet towards the nearest available wall about 50 cm (19-11/16")
away from the wall. (Fig. 2-2)
2
Install an optional air guide if the unit is installed in a location where strong winds
from a typhoon, etc. may directly enter the air outlet. (Fig. 2-3)
A
Air guide
3
Position the unit so that the air outlet blows perpendicularly to the seasonal wind
direction, if possible. (Fig. 2-4)
B
Wind direction
Fig. 2-1
Fig. 2-2
Fig. 2-3
Fig. 2-4
13+1
14-9/16
41-1
1/32
8-7/8
23-5/8
52-1
1
/16
(inch)
B
Total rated capacity
N%WXK