3. System
Parts name
Requirement
Flow switch
It is required to protect system from the effects of insufficient flow.
Flow sensor
It is required to detect an error in flow rate.
(The operation is validated with SIKA VVX20.)
It is required for Energy monitor function.
Strainer /Magnetic filter
(water circuit)
Provide it as required to protect parts from damages caused by iron particles/water/contamination (e.g. the position before pump and return
part from emitters).
Pressure relief valve
(Primary circuit side)
(Sanitary water side)
It is required to protect system from reaching high pressure.
Select the operating pressure depending on water pressure in the circuit in normal use.
Note: Follow the national regulations.
3-way valve
Current: 0.1 A Max. (If over 0.1 A you must use a relay)
Power supply: 230 V AC
Connect earth cable, if there is one.
Type: SPST
Note: SPDT type can NOT be used.
2-way valve
Current: 0.1 A Max. (If over 0.1 A you must use a relay)
Power supply: 230 V AC
Connect earth cable, if there is one.
Type: Normally closed
Select the 2-way valve that slowly opens and shuts off to prevent water hammer.
A by-pass valve or circuit should be installed between pump and 2-way valve for safety (to release pressure when the both 2-way valves are closed).
Select a 2-way valve equipped with manual override, which is necessary for topping up or draining of water.
Water circulation pump Current: 1.0A Max., Power supply: 230 V AC
When connecting a pump with an electric current of 1 A or multiple pumps, please note the following.
1. Use (a) relay(s).
2. When power is supplied from outdoor unit, TOTAL current (including the other parts) requirement MUST be 3 A. (otherwise, the fuse on
the outdoor unit PCB will blow. )
3. When independent power supplies (i.e. from the FTC unit itself) , total current for the pump(s) is 4 A. (otherwise, the fuse on the FTC
PCB will blow. )
Connect earth cable, if there is one.
Adjust the pump speed setting so that the flow rate in the primary circuit is appropriate for the outdoor unit installed see the table and figures below.
Outdoor heat pump unit
Water flow rate range [L/min]
Packaged model PUZ-WM50
6.5 - 14.3
PUZ-WM60
8.6 - 17.2
PUZ-WM85
10.8 - 25.8
PUZ-WM112
14.4 - 32.1
PUZ-HWM140
17.9 - 40.1
Split model
SUZ-SWM40
6.5 - 11.4
SUZ-SWM60
7.2 - 17.2
SUZ-SWM80
7.8 - 21.5
PUHZ-SW75
10.2 - 22.9
PUHZ-SW100
14.4 - 32.1
PUHZ-SW120
20.1 - 45.9
PUHZ-SW160
23.0 - 63.1
PUHZ-SW200
28.7 - 71.7
PUHZ-SHW80
10.2 - 22.9
PUHZ-SHW112
14.4 - 32.1
PUHZ-SHW140
17.9 - 40.1
PUHZ-SHW230
28.7 - 65.9
* The water velocity in pipes should be kept within certain limits of material to avoid erosion corrosion and excessive noise generation.
(e.g. Copper pipe: 1.5 m/s)
Continue to the next page.
3.4 Fourth step (Functions setting)
* Make sure to check the followings for your safety when designing a system. These are the minimum requirement for the safe use of FTC unit.
N
L
4 5 6
3-way valve
SPST type
N
L
4 5 6
3-way valve
motor
motor
SPDT type
TBO. 2