54
9. Multiple outdoor units control
Split model (SW1-3 to SW1-6)
Dip switch
Refrigerant address number
Add. 1
Add. 2
Add. 3
Add. 4
Add. 5
Add. 6
SW1-1
—
—
—
—
—
—
SW1-2
—
—
—
—
—
—
SW1-3
ON
OFF
ON
OFF
ON
OFF
SW1-4
OFF
ON
ON
OFF
OFF
ON
SW1-5
OFF
OFF
OFF
ON
ON
ON
SW1-6
OFF
OFF
OFF
OFF
OFF
OFF
Packaged model
Refer to outdoor unit installation manual.
<FTC: Main>
• Set Dip SW4-1 and SW4-2 to ON.
• For more details refer to “5. Dip Switch setting.”
<FTC: Sub>
• Set Dip SW4-1 to ON "Active :multiple outdoor unit control".
• Set Dip SW1-7 (Outdoor unit type) on each sub unit according to each connected outdoor unit type.
• Set only Dip-SW1-3 to ON on the sub unit that runs DHW operation.
Dip switch
Function
OFF
ON
Main
Sub
(PAC-SIF051B-E)
Sub *1
(Hydrobox)
SW1 SW1-1 Bolier
WITHOUT Bolier
WITH Bolier
—
—
SW1-2 Heat pump maximum outlet water
temperature
55˚C
60˚C
SW1-3 DHW tank
WITHOUT DHW tank
WITH DHW tank
SW1-4 Immersion heater
WITHOUT Immersion heater
WITH Immersion heater
—
—
SW1-5 Booster heater
WITHOUT Booster heater
WITH Booster heater
—
—
SW1-6 Booster heater function
For heating only
For heating and DHW
—
—
—
SW1-7 Outdoor unit type
Split type
Packaged type
—
SW1-8 Wireless remote controller
WITHOUT Wireless remote controller WITH Wireless remote controller
—
—
SW2 SW2-1 Room thermostat
1 input (IN1) logic change Zone1 operation stop at short
Zone1 operation stop at open
—
—
SW2-2 Flow switch 1 input (IN2) logic change
Failure detection at short
Failure detection at open
SW2-3 Booster heater capacity restriction
Inactive
Active
—
—
SW2-4 Cooling mode function
Inactive
Active
—
—
SW2-5
"Automatic switch to backup heater only
operation (When outdoor unit stops by error)"
Inactive
Active
—
—
SW2-6 Mixing tank
WITHOUT Mixing tank
WITH Mixing tank
*2
—
—
SW2-7 2-zone temperature control
Inactive
Active
—
—
SW2-8 Flow sensor
WITHOUT Flow sensor
WITH Flow sensor
—
SW3 SW3-1 Room thermostat 2 input (IN6) logic change Zone2 operation stop at short
Zone2 operation stop at open
—
SW3-2 Flow switch 2 and 3 input logic change Failure detection at short
Abnormality detection at open
—
SW3-3
—
—
—
—
—
SW3-4
—
—
—
—
—
SW3-5 Heating mode function
Inactive
Active
—
SW3-6 2-zone valve ON/OFF control
Inactive
Active
—
SW3-7
—
—
—
—
—
SW3-8
—
—
—
—
—
SW4 SW4-1 Multiple unit control
Inactive
Active
ON
ON
ON
SW4-2 Position of multiple outdoor units control Sub
Main
ON
OFF
OFF
SW4-3
—
—
—
—
—
—
SW4-4
—
—
—
—
—
—
SW4-5 Emergency mode (Heater only operation) Normal
"Emergency mode (Heater only operation)
(To be activated only when powered ON)"
—
—
SW4-6 Emergency mode (Bolier operation)
Normal
"Emergency mode (Bolier operation) (To
be activated only when powered ON)"
—
—
SW5 SW5-1
—
—
—
—
—
SW5-2 Advanced auto adaptation
Inactive
Active
—
SW5-3
—
—
—
—
—
SW5-4
—
—
—
—
—
SW5-5
—
—
—
—
—
SW5-6
—
—
—
—
—
SW5-7
—
—
—
—
—
SW5-8
—
—
—
—
—
SW6 SW6-1
—
—
—
—
—
SW6-2
—
—
—
—
—
SW6-3 Pressure sensor
Inactive
Active
—
SW6-4 Analog output signal (0-10 V)
Inactive
Active
—
SW6-5
—
—
—
—
—
: Setting is required
— : NO setting (function is not available)
*1 When FTC (Main) in Hydrobox is set as Sub.
*2 Set Dip SW2-6 to ON in "System 3 (2 zone)" and in "System 4 (with Boiler)" mentioned in "9.2 Pipe work."
en