41
(Continued to next page.)
Engineers Forms
Commissioning/Field settings record sheet
Main remote controller screen
Parameters
Default set-
ting
Field
setting Notes
Setting
Service menu
Thermistor adjustment
THW1
−10°C - +10°C
0°C
THW2
−10°C - +10°C
0°C
THW5B
−10°C - +10°C
0°C
THW6
−10°C - +10°C
0°C
THW7
−10°C - +10°C
0°C
THW8
−10°C - +10°C
0°C
THW9
−10°C - +10°C
0°C
THW10
−10°C - +10°C
0°C
THWB1
−10°C - +10°C
0°C
Auxiliary settings
Economy settings
for pump.
On/Off *6
On
Delay (3 - 60 min)
10 min
Electric heater
(Heating)
Space heating: On (used)/Off (not used)
On
Electric heater delay timer (5 - 180 min)
30 min
Electric heater
(DHW) *13
Booster heater
DHW: On (used)/Off (not used)
On
Immersion heater
DHW: On (used)/Off (not used)
On
Electric heater delay timer (15 - 30 min)
15 min
Mixing valve con-
trol
Running (10 - 240 sec)
120 sec
Interval (1 - 30 min)
2 min
Flow sensor *18
Minimum (0 - 100 L/min)
5 L/min
Maximum (0 - 100 L/min)
100 L/min
Analog output
Interval (1 - 30 min)
5 min
Priority (Normal/High)
Normal
Pump speed
DHW
Pump speed (1 - 5)
5
Heating/Cooling
Pump speed (1 - 5)
5
Heat source setting
Standard/Heater/Boiler/Hybrid *7
Standard
Heat pump setting
Heat pump flow rate range
Minimum (0 - 100 L/min)
5 L/min
Maximum (0 - 100 L/min)
100 L/min
Quiet mode
Day (Mon - Sun)
—
Time
0:00 - 23:45
Quiet level (Normal/ Level1/ Level2)
Normal
Operation
settings
Heating operation
*8
Flow temp.range
*10
Min.temp. (20 - 45°C)
30°C
Max.temp. (35 - 60°C)
50°C
Room temp.control
*15
Mode (Normal/Fast)
Normal
Interval (10 - 60min)
10min
Heat pump thermo
diff.adjust
On/Off *6
On
Lower limit (−9 - −1°C)
−5°C
Upper limit (+3 - +5°C)
5°C
Freeze stat function *11
Outdoor ambient temp. (3 - 20°C) / **
5°C
Simultaneous operation (DHW/
Heating)
On/Off *6
Off
Outdoor ambient temp. (−30 - +10°C) *3
−15°C
Cold weather function
On/Off *6
Off
Outdoor ambient temp. (−30 - −10°C) *3
−15°C
Boiler operation
Hybrid settings Outdoor ambient temp.
(−30 - +10°C) *3
−15°C
Priority mode
(Ambient/Cost/CO
2
) *17
Ambient
Outdoor ambient temp. rise
(+1 - +5 °C)
+3 °C
Intelligent
settings
Energy
price
*9
Electricity (0.001 - 999 */kWh) 0.5 */kWh
Boiler (0.001 - 999 */kWh)
0.5 */kWh
CO
2
emission
Electricity
(0.001 - 999 kg -CO
2
/kWh)
0.5 kg -CO
2
/
kWh
Boiler
(0.001 - 999 kg -CO
2
/kWh)
0.5 kg -CO
2
/
kWh
Heat
source
Heat pump capacity
(1 - 40 kW)
11.2 kW
Boiler efficiency
(25 - 150%)
80%
Booster heater 1 capacity
(0 - 30 kW)
2 kW
Booster heater 2 capacity
(0 - 30 kW)
4 kW