9.7 Connecting inputs/outputs
<Electrical connection for main controller>
• Refer to "4.5 Connecting inputs/outputs"
<Electrical connection for sub controller>
PAC-IF07*B-E
9. Multiple outdoor units control
Thermistor inputs
Name Terminal block Connector Item
Optional part model
TH2
—
CN21
Thermistor (Ref. liquid temp.)
—
THW1
—
CNW12 1-2 Thermistor (Flow water temp.)
—
THW2
—
CNW12 3-4 Thermistor (Return water temp.)
—
Note:
Do not splice the wiring to extend or shorten it, or this could affect correct monitoring of each temperature.
If the wiring is too long, bundle it with a strap to adjust the length.
Outputs
Name Terminal block Connector Item
OFF
ON
Signal/Max. current
OUT1
TBO.1 1-2
CNP1
Water circulation pump 1 output
OFF
ON
230V AC 1.0 A Max.
OUT4
TBO.2 4-6
CNV1
3-way valve (2-way valve 1) output
Heating
DHW
230V AC 0.1 A Max.
OUT13 TBO.4 3-4
—
2-way valve 2 output
DHW
Heating
230V AC 0.1 A Max.
<Fig. 9.7.2>
Signal inputs
Name Terminal block Connector Item
OFF (Open)
OFF (Short)
RC TBI.6 1-4
—
Communication cable between
indoor units
—
—
IN2 TBI.1 5-6
—
Flow switch 1 input
Refer to SW2-2 in <9.6 Dip Switch
Functions>.
Wiring specification and local supply parts
Item
Name
Model and specifications
Signal input function Signal input wire Use sheathed vinyl coated cord or cable.
Max. 10 m
Wire type: CV, CVS or equivalent
Wire size: Stranded wire 0.13 mm² to 1.25 mm²
Solid wire: ø0.4 mm to ø1.2 mm
Switch
Non-voltage “a” contact signals
Remote switch: minimum applicable load 12V DC, 1mA
L
N
OUT13
1 2 3 4 5 6
TBO.1
1 2 3 4 5 6
TBO.2
TBO.3 1 2 3 4 5 6 7 8
1 2 3 4
6
5
TBO.4
L
N
OUT1
L
N
OUT4
TBO.5 1 2 3 4 5 6 7 8
7 8
CN108
CN01
(BK)
1
3
CN3C
(BU)
CNPWM
(WH)
1
5
CNRF
(WH)
CN105
(RD)
CNIT
(BU)
1
2
CN20
(RD)
TBI.1
LED3
LED4
TAB1
8
1
2
3
4
5
6
1
2
3
4
5
6
7
8
CNP1
(WH)
TBO.1
1
5
3
1
5
SW6
1
3
1
5
1
5
LED2
1
SW1
8
1
SW2
8
1
SW3
1
SW4
6
8
1
SW5
LED1
1
3
1
3
CNP4
(RD)
TBO.2
1
2
3
4
5
6
TBO.3
CNV1
(WH)
1
3
5
1
2
3
4
5
6
7
8
TBO.4
CNIH
(OG)
1
3
CNBHT
(BK)
1
3
CN21
(YE)
1
3
CNW12
(RD)
1
4
CNW5
(BU)
1
4
1
4
CN1A
(WH)
6
8 7 5
2 1
TBI.2
6
8 7 5
2 1
TBI.3
6
8 7 5 4 2 1
TBI.4
6
8 7 5
2 1
TBI.5
6
8 7 5
2 1
6
8 7 5
2 1
TBI.6
1
4
CN401
(WH)
F2
F1
1
2
3
4
5
6
7
8
TBO.5
3
4 3
4 3
4 3
4 3
4 3
en
Note:
1. Do not connect multiple water circulation pumps directly to each output (OUT1). In such a case, connect them via (a) relay(s).
2. Stranded wire should be processed with insulation-covered bar terminal (DIN46228-4 standard compatible type).
Item
Name
Model and specifications
External output function Outputs wire
Use sheathed vinyl coated cord or cable.
Max. 30 m
Wire type: CV, CVS or equivalent
Wire size: Stranded wire 0.25 mm² to 1.5 mm²
Solid wire: 0.25 mm² to 1.5 mm²
Wiring specification and local supply parts
<Fig. 9.7.3>
Connect them using either way as shown above.
Outline view
Top view
<Fig. 9.7.1>
How to use TBO.1 to 5
Tool
Tool
Conductor
Conductor