100
9
E
Models
Power supply
Phase
Frequency &
Voltage
Input capacity
Indoor unit (A)
Main switch/Fuse
Outdoor unit (A)
Indoor unit
Wire No.
Power supply
Size mm (mm
2
)
Outdoor unit
Wire No.
Power supply
Size mm (mm
2
)
Earth wire
Size mm (mm
2
)
Indoor unit/Outdoor unit connecting
Wire No.
×
size mm (mm
2
)
Control circuit rating
Indoor unit power supply
PSH-3GJHA
PSH-4GJSA
PSH-3GJHA
PSH-4GJHSA
PSH-5GJHSA
PSH-6GJHSA
~/N (Single)
3
50 Hz, 220-240 V
60 Hz, 220 V
50 Hz, 380/220-415/240 V (4 Wires)
15/15
15/15
15/15
30/20
30/20
30/20
60/50
60/50
30/20
30/20
30/20
30/30
2
2
2
2
2
2
1.6 (2.0)
1.6 (2.0)
1.6 (2.0)
2.0 (3.5)
2.0 (3.5)
2.0 (3.5)
2
3
4
4
4
4
2.6 (5.5)
2.6 (5.5)
1.6 (2.0)
1.6 (2.0)
2.0 (3.5)
2.0 (3.5)
2.0 (3.5)
2.0 (3.5)
1.6 (2.0)
1.6 (2.0)
1.6 (2.0)
1.6 (2.0)
3
×
0.8 (0.5) or Cable 3C
×
(0.3), (Polar)
DC12 V
~/N (Single phase), 50 Hz, 220-240 V or 60 Hz, 220 V
9. Field electrical wiring (Power wiring specifications)
Wir
ing
Models
Power supply
Phase
Frequency &
Voltage
Input capacity
Indoor unit (A)
Main switch/Fuse
Outdoor unit (A)
Indoor unit
Wire No.
Power supply
Size mm
2
Outdoor unit
Wire No.
Power supply
Size mm
2
Indoor unit/Outdoor unit connecting
Wire No.
×
size mm (mm
2
)
Control circuit rating
Indoor unit power supply
Wir
ing
PS-3GJA
PS-4GJSA
PS-4GJSA
PS-5GJSA
PS-6GJSA
PS-3GJA
PS-4GJSA
PS-5GJSA
PS-6GJSA
~/N (Single)
3 ~ (3ph)
50 Hz : 3N ~ (3ph, 4 wires), 60 Hz : 3 ~ (3ph)
50 Hz, 220-240 V
60 Hz, 220 V
50 Hz, 380/220-415/240 V
60 Hz, 220 V
60 Hz, 380/220 V (PS-4-6GJSA)
16/16
16/16
16/16
16/16
16/16
16/16
16/16
16/16
16/16
63/63
100/75
63/63
60/50
100/75
32/25
32/32
32/32
32/32
3
3
3
3
3
3
3
3
3
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
3
3
4
4
4
5
5
5
5
6
10
6
6
10
2.5
2.5
4
4
2
×
0.8 (0.5) or Cable 2C
×
(0.3)...non-Polar
DC12 V
~/N (Single phase), 50 Hz, 220-240 V or 60 Hz, 220 V
Notes:
1. Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water, etc.) when proceeding with wiring and connections.
2. Wire size are the minimum necessary for metal conduit wiring. Power wires size should be 1 rank thicker, in consideration of voltage drops.
3. Earth wire is connected to both indoor unit and outdoor units.
4. This table shows an example of field electrical wiring. Details should be based on applicable technical standards.