3. SIGNALS AND WIRING
(c) Alarm occurrence
POINT
When the overcurrent alarm (32) occurs, the dynamic brake is not
operated.
Servo motor speed
ON
OFF
Base circuit
Electromagnetic
brake (CNP2-9)
Invalid (ON)
Valid (OFF)
Trouble (ALM)
No (ON)
Yes (OFF)
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
operation delay time
Electromagnetic brake
(10ms)
(d) Main circuit power off
When main circuit power switches off, the undervoltage alarm (10) occurs and the operation timing
is as shown in (c) of this section.
(e) Control circuit power off
POINT
When the control circuit power is switched off, the dynamic brake is not
operated.
20ms
ON
OFF
Electromagnetic brake
Servo motor speed
Control circuit power
(P24L)
Coasting