MELSEC-WS
Data sets
47
Byte Bit
Safety I/O modules
(e.g. WS0-XTIO, WS0-XTDI)
CPU modules
(e.g. WS0-CPUx)
Network modules
(e.g. WS0-GETH)
0
6
Output fast shut off logic control time
out
1 = No error
0 = Time out exceed because the
control signal from CPU logic has not
switched off within 1s
EFI 1 communication failure
1 = No error
0 = Error
Output status
1 = Valid network
communication
0 = Invalid or no
communication
7
Reserved
EFI 2 communication failure
1 = No error
0 = Error
Reserved
1
0
Input 1-2 dual channel input evaluation
error
1 = No error
0 = Error
Reserved Reserved
1
Input 3-4 dual channel input evaluation
error
1 = No error
0 = Error
2
Input 5-6 dual channel input evaluation
error
1 = No error
0 = Error
3
Input 7-8 dual channel input evaluation
error
1 = No error
0 = Error
4
Reserved
5
Reserved
6
Reserved
7
Reserved
2
0
Input 1 external test signal failure.
1 = No error
0 = Error
1
Input 2 external test signal failure.
1 = No error
0 = Error
2
Input 3 external test signal failure.
1 = No error
0 = Error
Содержание Melsec WS Series
Страница 1: ...Safety Controller Ethernet Interface Module User s Manual WS0 GETH ...
Страница 2: ......
Страница 89: ...Procedures before operation MELSEC WS 86 ...
Страница 90: ...MELSEC WS Procedures before operation 87 ...
Страница 91: ...Procedures before operation MELSEC WS 88 ...
Страница 97: ...Procedures before operation MELSEC WS 94 ...
Страница 98: ...MELSEC WS Procedures before operation 95 ...
Страница 99: ...Procedures before operation MELSEC WS 96 ...
Страница 108: ...MELSEC WS Procedures before operation 105 Sample program auto update mode Figure 62 Sample program auto update mode ...
Страница 141: ......