Ethernet interface module
MELSEC-WS
18
Make sure that the voltage supply of the MELSEC-WS safety controller is
switched off.
Hang the device onto the DIN rail (1)).
Connect the Ethernet interface module directly onto the right side of the CPU
module of the MELSEC-WS safety controller. Up to two network modules per
system are possible.
Ensure that the earthing spring contact is positioned correctly (2)). The earthing
spring contact of the module must contact the DIN rail securely to allow
electrical conductivity.
Latch the module onto the DIN rail by pressing it lightly in the direction of the
arrow (3)).
If there are several modules, slide the modules together individually in the
direction of the arrow until the side plug connection latches in.
Install the end clips on the right and left.
The following steps are necessary after mounting:
Complete the electrical connections (See Section 3.3.)
Configuration (See Section 3.4 and the Safety Controller Setting and Monitoring
Tool Operating Manual.)
Checking the installation (see the Safety Controller User’s Manual.)
3)
2)
1)
Figure 2:
Mounting the module
onto the DIN rail
Figure 3:
Installing the end clips
Содержание Melsec WS Series
Страница 1: ...Safety Controller Ethernet Interface Module User s Manual WS0 GETH ...
Страница 2: ......
Страница 89: ...Procedures before operation MELSEC WS 86 ...
Страница 90: ...MELSEC WS Procedures before operation 87 ...
Страница 91: ...Procedures before operation MELSEC WS 88 ...
Страница 97: ...Procedures before operation MELSEC WS 94 ...
Страница 98: ...MELSEC WS Procedures before operation 95 ...
Страница 99: ...Procedures before operation MELSEC WS 96 ...
Страница 108: ...MELSEC WS Procedures before operation 105 Sample program auto update mode Figure 62 Sample program auto update mode ...
Страница 141: ......