Ethernet interface module
MELSEC-WS
26
3.4.5
Verification of a configuration
After the configuration has been transferred successfully, the MELSEC-WS safety
controller can be verified. To this purpose, the downloaded configuration data are
read back out from the safety controller and compared with the project data. If they
match, the data are displayed in a report. If the user confirms that they are correct,
the safety controller is considered to be verified.
In the
Hardware
configuration
view, click the icon
Upload and verify
configuration
and compare the configuration. The
Upload and verify result
window is opened.
Click
Yes
below at the question
Set device to verified?
if the displayed
configuration is the expected configuration. The safety controller is then
considered to be verified.
You have to be logged in as an Administrator in order to mark the device as
“verified”.
If the verification is completed successfully, a “Read in and compare” report that
provides the most important project information is created subsequently. You can
print out or store this report.
The status verified/not verified is indicated in the lower right-hand corner of the
Setting and Monitoring Tool and by the CV LED of the CPU module turning on.
Only if the device and the corresponding configuration have been marked as
verified, the Auto RUN Mode is active in the configuration of the CPU module. If
the configuration is not set to verified, the safety controller stays in Idle mode (CV
LED on the CPU module flashing) after power up and needs to be set to
Run
Mode
using the Setting and Monitoring Tool.
If differences between the project data and the read-back configuration data are
detected, a corresponding message including information about possible actions
is displayed. Verification of the configuration is not possible then. Observe the
information in the error message for the further procedure. Terminate the dialog
box by clicking
Close
.
If you change a verified configuration, the status is reset to “not verified”.
Exception
: If you make only non safety-related changes such as modifying the
Ethernet interface module name, the Ethernet interface module’s IP address or
the port number for a TCP/IP socket connection, the configuration status remains
“verified”.
More information can be found in the Safety Controller Setting and Monitoring Tool
Operating Manual.
3.4.6
Upload of a configuration
When in online mode, you can upload a configuration from the connected MELSEC-
WS safety controller:
Click on
Upload
. The current configuration of the safety controller will be loaded
into the Setting and Monitoring Tool and can be edited after going offline.
Note
Содержание Melsec WS Series
Страница 1: ...Safety Controller Ethernet Interface Module User s Manual WS0 GETH ...
Страница 2: ......
Страница 89: ...Procedures before operation MELSEC WS 86 ...
Страница 90: ...MELSEC WS Procedures before operation 87 ...
Страница 91: ...Procedures before operation MELSEC WS 88 ...
Страница 97: ...Procedures before operation MELSEC WS 94 ...
Страница 98: ...MELSEC WS Procedures before operation 95 ...
Страница 99: ...Procedures before operation MELSEC WS 96 ...
Страница 108: ...MELSEC WS Procedures before operation 105 Sample program auto update mode Figure 62 Sample program auto update mode ...
Страница 141: ......