Ethernet interface module
MELSEC-WS
34
Parameter Length
Value
Command WORD
00F1
H
= Data set(s) request message
Request data
set 1
WORD
0 = Do not send data set 1.
1 = Send data set 1.
Request data
set 2
WORD
0 = Do not send data set 2.
1 = Send data set 2.
Request data
set 3
WORD
0 = Do not send data set 3.
1 = Send data set 3.
Request data
set 4
WORD
0 = Do not send data set 4.
1 = Send data set 4.
The response message is returned to the application by the Ethernet interface
module. The response message telegram will be structured as shown below:
Parameter Length
Value
Command WORD
001F
H
= Data set(s) response message
Data set 1
length
WORD
0 = Data set not returned in data set(s) data field
Non-zero = Length of data set
Data set 2
length
WORD
0 = Data set not returned in data set(s) data field
Non-zero = Length of data set
Data set 3
length
WORD
0 = Data set not returned in data set(s) data field
Non-zero = Length of data set
Data set 4
length
WORD
0 = Data set not returned in data set(s) data field
Non-zero = Length of data set
Data set(s)
data
Array of
bytes
Data set(s) information
Output data set writing
The following command message is sent by the application to the Ethernet interface
module to write to the output data sets:
Parameter Length
Value
Command WORD
00F2
H
= Set output data set(s) command message
Output data
set 1 length
WORD
0 = Output data set not included in data set(s) data field
Non-zero = Length of data set (10 bytes)
Output data
set 2 length
WORD
0 = Output data set not included in data set(s) data field
Non-zero = Length of data set (10 bytes)
Output data
set 3 length
WORD
0 = Output data set not included in data set(s) data field
Non-zero = Length of data set (10 bytes)
Output data
set 4 length
WORD
0 = Output data set not included in data set(s) data field
Non-zero = Length of data set (10 bytes)
Output data
set 5 length
WORD
0 = Output data set not included in data set(s) data field
Non-zero = Length of data set (10 bytes)
Data set(s)
data
Array of
bytes
Data set(s) information
Table 6:
Input data set read
request
Table 7:
Input data set read
response
Table 8:
Output data set write
request
Содержание Melsec WS Series
Страница 1: ...Safety Controller Ethernet Interface Module User s Manual WS0 GETH ...
Страница 2: ......
Страница 89: ...Procedures before operation MELSEC WS 86 ...
Страница 90: ...MELSEC WS Procedures before operation 87 ...
Страница 91: ...Procedures before operation MELSEC WS 88 ...
Страница 97: ...Procedures before operation MELSEC WS 94 ...
Страница 98: ...MELSEC WS Procedures before operation 95 ...
Страница 99: ...Procedures before operation MELSEC WS 96 ...
Страница 108: ...MELSEC WS Procedures before operation 105 Sample program auto update mode Figure 62 Sample program auto update mode ...
Страница 141: ......