Set-up menu
DISPLAY
SET
1
Pulse output
item 1
1
Set the element to be output to pulse output 1.
At initial, imported active energy is set to pulse output 1,
accordingly, normally press the SET to go to the next setting.
DISPLAY
SET
DISPLAY
SET
Example of pulse output 1
2
Pulse output item 1
pulse value
2
Set the pulse value of pulse output 1.
Pulse value is selected from the table below, according to total
load [kW].
Total load [kW] =
✽
Primary voltage value is calculated by phase to newtral.
1000
α
×
(Primary voltage)
×
(Primary current)
α=
3 (Three-phase 4-wire)
α=
3 (Three-phase 3-wire)
+
–
,
+
–
,
+
–
,
3
Pulse output
item 2
+
–
,
Example of pulse output 1
Example of pulse output 2
4
Pulse output item 2
pulse value
+
–
,
Set the set-up menu number to “7”. (Set as shown in the right
display.)
Pulse output element
Imported active energy (Pulse output 1)
Exported active energy
Imported lag reactive energy (Pulse output 2)
Imported lead reactive energy
Exported lag reactive energy
Exported lead reactive energy
No output
Display
Wh
– Wh
varh (LAG)
varh (LEAD)
– varh (LAG)
– varh (LEAD)
non
Settable elements
DISPLAY
SET
DISPLAY
SET
3
Set the element to be output to pulse output 2.
Pulse output 2 is set also in the same method as
q
pulse output item 1 set-up.
(At initial, imported lag reactive energy is set to pulse output 2.)
In case of reactive energy, kW in the above table is exchanged into kvar, and kWh into kvarh.
Total load [kW]
1 or higher and below 10
10 or higher and below 100
100 or higher and below 1000
1000 or higher and below 10000
10000 or higher and below 100000
100000 or higher
Settable pulse value [kW/pulse]
1
10
100
1
10
100
0.1
1
10
0.1
1
10
0.01
0.1
1
0.01
0.1
1
0.001
0.01
0.1
0.001
0.01
0.1
kWh/Pulse
kWh/Pulse
kWh/Pulse
MWh/Pulse
MWh/Pulse
MWh/Pulse
4
Set the pulse value of pulse output 2.
Pulse output 2 is set also in the same method as
w
pulse output item 1 set-up.
In the operation mode, press the
SET
and the
RESET
simultaneously for 2 seconds or more, and the following
operation becomes available.
When the ME-4201-NS96 type optional plug-in module is not installed, this menu cannot be set.
4. Set-up
4.8 Pulse Output Set-up
Set-up Menu 7