When the ME-0052-NS96 type optional plug-in module is installed, simulated signal output to test the digital
output circuit can be put out.
Operate it according to the following.
The following operation becomes possible when you turn on the power supply while pressing the
DISPLAY
at the
state of power failure.
It is impossible to test without the optional plug-in module.
5.5 Digital Output Test
Test menu
SET
SET
Set the test menu number to “4”. (Set as shown in the right
display.)
Test menu
In case of test the other output, according to the 5.2 to 5.4,
continue to the test.
When the test is finished, turn off the power supply.
+
–
,
+
–
,
q
Digital output
CH1 test
+
–
,
SET
w
Digital output
CH2 test
+
–
,
Note: An initial value of each CH of this test mode is “Open”. If CH is changed or this test mode ends, the output becomes “Open” .
q
Test the digital output CH1.
When the , is pressed, the display and the contact
output are changed as following.
+
–
oFF
(Opened)
on
(Closed)
w
Test the digital output CH2.
When the , is pressed, the display and the contact
output are changed as following.
+
–
oFF
(Opened)
on
(Closed)
5. Output Adjustment and How to Test