33
When the ME-4201-NS96 type optional plug-in module is installed, simulated signal output to test the alarm output
circuit can be put out.
Operate it according to the following.
The following operation becomes possible when you turn on the power supply while pressing the
DISPLAY
at the
state of power failure.
It is impossible to test without the option module.
5.2 Alarm Output Test
q
Test the alarm output.
When the , is pressed, the display and the contact
output are changed as following.
+
–
Test menu
q
Alarm output test
SET
SET
Set the test menu number to “1”. (Set as shown in the right
display.)
Test menu
In case of test the other output, according to the 5.3 to 5.5,
continue to the test.
When the test is finished, turn off the power supply.
+
–
,
+
–
,
+
–
,
oFF
(Opened)
on
(Closed)
5. Output Adjustment and How to Test