15
4. Set-up
4.2 Basic Set-up
Set-up Menu 1
6
VT primary
voltage
7
CT secondary
current
6
Set the primary voltage value of VT in the case of using VT.
If you set “no” on set-up No.
3
, this display does not appear.
Initial value
Three phase 3-wire : 10000V
Three phase 4-wire : 200V
7
Set the secondary current value of CT.
DISPLAY
SET
DISPLAY
SET
5
VT secondary
voltage
DISPLAY
SET
5
Set the secondary voltage values of VT in case of using VT.
If you set “no” on set-up No.
3
, this display does not appear.
63.5V
100V
110V
115V
120V
SET DISPLAY
8
CT primary
current
8
Set the primary current value of CT. (The initial value is 5A.)
DISPLAY
SET
Three phase 4-wire
100V
110V
220V
Three phase 3-wire
5A
1A
+
–
,
+
–
,
SET DISPLAY
+
–
,
+
–
,
•
•
•
•
✽
•
From top digit, select the value of the flickering digit by and .
The setting digit can be moved to right by the SET .
The setting digit can be moved to left by the DISPLAY .
The number of settable digits is 3 digits. Setting is available in the range from 60V to 750kV. (750000V)
If it is set to other range than 60V to 750kV, error display (E05) appears. At the moment of the
error display, press the SET , and review the set value, and set it once again.
When the SET is pressed at the most lower digit, the setting item goes to the next one.
+
–
•
•
•
•
✽
•
From top digit, select the value of the flickering digit by and .
The setting digit can be moved to right by the SET .
The setting digit can be moved to left by the DISPLAY .
The number of settable digits is significant 2 digits. Setting is available in the range from 5A to 30kA (30000A).
If it is set to other range than 5A to 30kA, error display (E05) appears. At the moment of the error
display, press the SET , and review the set value, and set it once again.
When the SET is pressed at the most lower digit, the setting item goes to the next one.
+
–