20
4
Set the back light auto off (Auto)/continuous on (HoLd).
(Setting this is normally unnecessary.)
If you set to ‘Auto off’, the back light turn off when there is no
key operation for 5 minutes. When an operation key is pressed,
it is lit for 5 minutes. At this moment, the display is not changed.
When the operation key is pressed once again, the display is
changed.
Auto
(Auto OFF)
HoLd
(Continuous ON)
Set-up menu
DISPLAY
SET
1
Expanded counting
1
Set the combination of display for active energy and reactive energy.
Combination of imported/exported and lag/lead can be selected.
Combination
1
in the diagram is the standard use.
Combination
!
@
#
$
Active energy
(Wh)
Reactive energy
(varh)
2
Harmonics
3
Digital input/output
2
Set the harmonic measurement.
on : Harmonic measurement value is displayed.
off : Harmonic measurement value is not displayed.
on : The state of the digital input/output is displayed.
off : The state of the digital input/output is not displayed.
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
3
Set the display of the digital input/output state.
When the ME-0052-NS96 or ME-0040C-NR96 type optional
plug-in module is not installed, this menu cannot be set.
+
–
,
+
–
,
+
–
,
+
–
,
+
–
,
4
Back light
ON/OFF setting
Set the set-up menu number to “4”. (Set as shown in the right
display.)
Imported Exported
Imported
lag
(Exported)
(lead)
lag
lead
Imported
lead
(Exported)
(lag)
Imported
lag
lead
Exported
Display of combination
!
Display of combination
@
Display of combination
#
Display of combination
$
4. Set-up
4.5 Display of Each Measurement, etc. Set-up
Set-up Menu 4
In the operation mode, press the
SET
and the
RESET
simultaneously for 2 seconds or more, and the following
operation becomes available.