11
MAC-333IF-E
5.3 REMOTE CONTROL
(1) Card key connection (Switch will open by insertion of the card key.)
Switch will open by insertion of the card key, which stops the room air conditioner.
Function
summary
System
configuration
ON
1
2
3
4
5
6
7
8
OFF
ON
1
2
3
4
5
6
7
8
OFF
MAC333IF-E
CN591
3
2
1 Brown
Red
Orange
Insulate here.
The card key must be the one that
· opens the switch when inserted.
· can be used on the following condition:
12 VDC, 0.5 to 2.0 mA
a
SYSTEM CONTROL Interface
Behavior
· When the card is inserted (and the switch opens), the ON/OFF operation from the paired remote controller is enabled.
· When the card is removed (and the switch closes), the air conditioner stops and the ON/OFF operation from the paired remote controller
is prohibited.
* “Paired remote controller” includes the wireless remote controller that comes with the room air conditioner, the MA remote controller,
and the ME remote controller.
Switch setting
· Card key connection (Switch will open by insertion of the card key.)
SW No.
Dip switch
Operating details
SW500
SW502
· SW502-2,3,4,6: OFF
· SW502-5: ON
· SW500-6,8: OFF
· Cable type
a: Sheathed cable, size 0.3 mm
2
or more
Specifications
of communication
cable
· Cable length
a: Cable size is 0.3 mm
2
: 50 m or less / Cable size is 0.5 mm
2
: 100 m or less
Note
· The operation of the paired remote controller prohibited by the card key is the ON/OFF operation only.
Other operations, such as setting the temperature, are enabled.
· When the interface is connected to the M-NET system, even though the card key prohibits the operation with the paired remote
controller, the ON/OFF operation with the system controller is enabled.
· When the interface is connected to the M-NET system, if the system controller prohibits the manual ON/OFF operation, the ON/OFF
operation with the card key is prohibited. To enable the card key, do not disable the manual operation on the system controller.
· When the group setting is made with the M-NET system or the MA remote controller, connect the card key to the interface with the
lowest M-NET address or refrigerant address. The wireless remote controller cannot be used together.
Содержание MAC-333IF-E
Страница 1: ...2012 SYSTEM CONTROL INTERFACE Model MAC 333IF E TECHNICAL MANUAL ...
Страница 2: ...B ...
Страница 29: ......
Страница 30: ......
Страница 31: ......