MAC-333IF-E
(4) Relay outputs of ON/OFF signal and humidifier control signal
ON/OFF signal of the room air conditioner and humidifier control (ON/OFF) signal can be output to the relay.
· Relay 1
· Relay 1 is ON when the air conditioner is on.
· Relay 1 is OFF when the air conditioner is off.
· Relay 2
· Relay 2 is ON when the conditions to operate the external humidifier are satisfied.
(Conditions to operate the humidifier: The air conditioner is operating in the heating or the automatic heating mode.)
· Relay 2 is OFF when the conditions to stop the external humidifier are satisfied.
(Conditions to stop the humidifier: The air conditioner is not operating or it is operating in a mode other than the heating or the
automatic heating mode.)
ON
1
2
3
4
5
6
7
8
OFF
ON
OFF
ON
1
2
3
4
5
6
7
8
OFF
Function
summary
System
configuration
MAC333IF-E
C
R1
TB571
R2
TB530
DC power
source
12 V
DC power source
12 VDC (+10 %, -0 %), 5 W or more
a
b
SYSTEM CONTROL interface
* External power source is required for the status output and the control signal output.
Behavior
Switch setting
Specifications
of communication
cable
Note
Relay 1, 2
Coil rating: 12 VDC, 75 mA or less
Relay 1
Relay 2
· Output change
Change the output logic.
SW No.
Dip switch
Operating details
SW502
· OFF:
· It behaves as described in the “Behavior” section in this chart.
· ON:
· Relay 1
· Relay 1 is OFF when the air conditioner is on.
· Relay 1 is ON when the air conditioner is off.
· Relay 2
· Relay 2 is OFF when the conditions to operate the external humidifier are satisfied.
· Relay 2 is ON when the conditions to stop the external humidifier are satisfied.
· Output setting
Make settings for outputs of ON/OFF and external humidifier
SW No.
Dip switch
Operating details
SW500
· SW500-5: ON
· SW500-4,8: OFF
·
Cable type
· a: Sheathed cable (Stranded cable), size 0.3 mm
2
to 1.25 mm
2
/ Sheathed cable (Solid cable), size ø0.4 mm to ø1.2 mm
· b: Use the cable specified for the external power source. Its size must be from 0.3 mm
2
to 1.25 mm
2
.
·
Cable length
· a: Cable size is 0.3 mm
2
: 50 m or less / Cable size is 0.5 mm
2
: 100 m or less
· b: Follow the requirement for the external power source.
· External power source is required for the status output.
· TB530 and TB571 have polarities, so check them before connection.
· Do not connect DC power source to TB571.
· When a relay with a built-in diode is used, take care to choose the correct polarity.
TB571 C: + potential
TB571 R1 and R2: - potential