MAC-333IF-E
(6) Details of remote control (for giving priority to operation performed by continuous contact switch)
Brown
Red
Orange
Function
summary
The operation can be started/stopped or enabled/disabled according to the operation by continuous contact switches.
System
configuration
Behavior
· Switch 1
· When Switch 2 is closed, opening Switch 1 stops the air conditioner.
· When Switch 2 is closed, closing Switch 1 operates the air conditioner.
· Switch 2
· When it opens, the ON/OFF operation with the paired remote controller and the M-NET system controller is enabled, and the operation
from Switch 1 is prohibited.
· When it closes, the ON/OFF operation with the paired remote controller and the M-NET system controller is prohibited, and the operation
from Switch 1 is enabled.
* “Paired remote controller” includes the wireless remote controller that comes with the room air conditioner, the MA remote controller,
and the ME remote controller.
MAC333IF-E
CN591
3
2
1
Switch 1
Switch 2
a
· The switches can be used on the following condition:
12 VDC, 0.5 to 2.0 mA
SYSTEM CONTROL Interface
Switch setting
· Input mode (continuous contact)
Make settings for the continuous contact switches.
SW No.
Dip switch
SW No.
Dip switch
Operating details
SW500
· SW502-2: OFF
· SW500-6,8: OFF
· SW502-3: ON
· Input change
Change the input logic.
Operating details
SW502-4
· OFF:
· It behaves as described in the “Behavior” section in this chart.
· ON:
· Switch 1
· When Switch 2 is open, opening Switch 1 operates the air conditioner.
· When Switch 2 is open, closing Switch 1 stops the air conditioner.
· Switch 2
· When Switch 2 opens, the ON/OFF operation with the paired remote controller and
the M-NET system controller is prohibited, and the operation from Switch 1 is enabled.
· When Switch 2 closes, the ON/OFF operation with the paired remote controller and
the M-NET system controller is enabled, and the operation from Switch 1 is prohibited.
· Cable type
a: Sheathed cable, size 0.3 mm
2
or more
Specifications
of communication
cable
· Cable length
a: Cable size is 0.3 mm
2
: 50 m or less / Cable size is 0.5 mm
2
: 100 m or less
Note
·The operation of the paired remote controller prohibited by Switch 2 is the ON/OFF operation only.
Other operations, such as setting the temperature, are enabled.
· When the interface is connected to the M-NET system, if Switch 2 prohibits the operation with the paired remote controller,
the ON/OFF operation with the system controller is disabled.
· When the interface is connected to the M-NET system, even if the system controller prohibits the manual ON/OFF operation,
the state of Switch 1, when the operation with Switch 2 is prohibited, is prioritized. To enable the Switch 1 and 2, do not disable the
manual operation prohibition on the system controller.
· When the group setting is made with the M-NET system or the MA remote controller, connect Switch 1 and 2 to the interface with the
lowest M-NET address or refrigerant address. The wireless remote controller cannot be used together.
ON
1
2
3
4
5
6
7
8
OFF
SW502
ON
1
2
3
4
5
6
7
8
OFF
ON
1
2
3
4
5
6
7
8
OFF
ON
OFF