5
MAC-333IF-E
• To connect the interface to the system controller and/or ME remote controller, connect the M-NET communication cable to
TB520 (non-polarized).
Connect the 2-core communication cable to A1&B1 or A2&B2. (It does not matter which pair of connectors is used.)
• Connect the shield wire of the connecting cable to the S terminal only when the daisy chain method is used to wire the com-
munication cable.
• M-NET communication cable should be located as far away from other power supply cords as possible. Placing them closely
could cause a malfunction.
• After wiring is complete,
fi
x each cable with the cable clamps, and attach the cable ties as shown in the
fi
gure.
(3) Connecting the M-NET communication cable
●
For connection of the MA remote controller, connect the MA
remote control cable to TB580 (non-polarized).
●
When more than one unit of room air conditioner is operated
in group control, use the daisy chain wiring method by con-
necting the MA remote control cable to TB580.
(4) Connecting to the MA remote controller
• Before performing the following procedures, turn off the main power to the
air conditioner and all systems.
• If the connecting cable is not securely
fi
xed, the connector may come off,
and the interface could break or malfunction.
• The unit will not operate normally if the dip switches (SW500, SW502) and the
rotary switches (SW501, SW510, SW580) on the interface unit are not set cor-
rectly.
• Replace the cable clamp according to the size of the connecting cable used
for each system. Fasten the cable tie as shown in the
fi
gure to prevent undesirable movement of the connecting cable.
(2) Connecting to the systems
Mounting screw
Connecting cable
for each system
Cable ties
Cable clamp
A1 B1 A2 B2
S
A1 B1 A2 B2
S
Shield
Shield
Communication cable
(M-NET transmission cable)
Communication cable
(M-NET transmission cable)
Communication cable
(M-NET transmission cable)
ME remote controller cable
ME remote controller
Cable ties
Cable ties
Cable tie
Mounting
screw
Cable ties
Cut here with nippers along the notches. Make sure the
cut surface is free of any burr which could damage the
connecting cable and the ME remote control cable.
Cable clamps
(Large)
or (Medium)
Mounting screw
Cable clamp
(Large) or
(Medium)
Cable clamp
(Large)
or (Medium)
Mounting screw
Mounting screw
The interfaces are daisy chained
using the communication cable.
Daisy chain method is NOT used
to wire the communication cable
The interfaces are daisy chained using the communi-
cation cable, and ME remote controller is used
Daisy chain method is used to
wire the communication cable
Note
When the interfaces are daisy chained
via the same terminal block, use
1.25mm
2
connecting cables.
MA remote controller
Connect to the MA remote
controller or Interface unit
MA remote con-
trol cable
Cable ties
Cable clamp
(Large) or
(Medium)
Mounting
screw