background image

5

MAC-333IF-E

• To connect the interface to the system controller and/or ME remote controller, connect the M-NET communication cable to 

TB520 (non-polarized).

  Connect the 2-core communication cable to A1&B1 or A2&B2. (It does not matter which pair of connectors is used.)

• Connect the shield wire of the connecting cable to the S terminal only when the daisy chain method is used to wire the com-

munication cable.

• M-NET communication cable should be located as far away from other power supply cords as possible. Placing them closely 

could cause a malfunction.

• After wiring is complete, 

fi

 x each cable with the cable clamps, and attach the cable ties as shown in the 

fi

 gure.

(3) Connecting the M-NET communication cable

 For connection of the MA remote controller, connect the MA 

remote control cable to TB580 (non-polarized).

 When more than one unit of room air conditioner is operated 

in group control, use the daisy chain wiring method by con-

necting the MA remote control cable to TB580.

(4) Connecting to the MA remote controller

• Before performing the following procedures, turn off the main power to the 

air conditioner and all systems.

• If the connecting cable is not securely 

fi

 xed, the connector may come off, 

and the interface could break or malfunction.

• The unit will not operate normally if the dip switches (SW500, SW502) and the 

rotary switches (SW501, SW510, SW580) on the interface unit are not set cor-

rectly.

• Replace the cable clamp according to the size of the connecting cable used 

for each system. Fasten the cable tie as shown in the 

fi

 gure to prevent undesirable movement of the connecting cable.

(2) Connecting to the systems

Mounting screw

Connecting cable 
for each system

Cable ties

Cable clamp

A1 B1 A2 B2

S

A1 B1 A2 B2

S

Shield

Shield

Communication cable
(M-NET transmission cable)

Communication cable 
(M-NET transmission cable)

Communication cable
(M-NET transmission cable)

ME remote controller cable

ME remote controller

Cable ties

Cable ties

Cable tie

Mounting 
screw

Cable ties

Cut here with nippers along the notches. Make sure the 
cut surface is free of any burr which could damage the 
connecting cable and the ME remote control cable.

Cable clamps
(Large) 
or (Medium)

Mounting screw

Cable clamp 
(Large) or 
(Medium)

Cable clamp 
(Large) 
or (Medium)

Mounting screw

Mounting screw

The interfaces are daisy chained 

using the communication cable.

Daisy chain method is NOT used 

to wire the communication cable

The interfaces are daisy chained using the communi-

cation cable, and ME remote controller is used

Daisy chain method is used to 

wire the communication cable

Note

When the interfaces are daisy chained
 via the same terminal block, use 

1.25mm

2

 connecting cables.

MA remote controller

Connect to the MA remote 
controller or Interface unit

MA remote con-
trol cable

Cable ties

Cable clamp 
(Large) or 
(Medium)

Mounting 
screw

Содержание MAC-333IF-E

Страница 1: ...2012 SYSTEM CONTROL INTERFACE Model MAC 333IF E TECHNICAL MANUAL ...

Страница 2: ...B ...

Страница 3: ...2 2 INSTALLATION OF INTERFACE UNIT 4 3 CONNECTION 4 4 SETTING OF DIP SWITCH AND ROTARY SWITCH 7 5 FUNCTIONS 8 5 1 M NET CONNECTION 8 5 2 MA REMOTE CONTROLLER CONNECTION 9 5 3 REMOTE CONTROL 11 5 4 STATUS SIGNAL OUTPUT 20 5 5 ON OFF CONTROL BY MAIN POWER SOURCE 25 6 IMPORTANT NOTE 26 ...

Страница 4: ...normal signals ON OFF control by main power source Turning M series on when the main power is turned on S series Indoor unit s connected to SUZ or MXZ series The following table shows the restrictions on the combination use of the functions ON OFF control by main power source can be used regardless of the following combinations however ON OFF control by main power source cannot be used with AUTO r...

Страница 5: ...mmunication with connected equipment For details refer to 3 5 Checking the communication status in this manual Function setting switch B For details refer to 4 SETTING OF DIP SWITCHAND ROTARY SWITCH in this manual Function setting switch A For details refer to 4 SETTING OF DIP SWITCHAND ROTARY SWITCH in this manual LED for checking communica tion with connected equipment For details refer to 3 5 C...

Страница 6: ...the following procedures turn off the main power to the air conditioner Connect the connecting cable 5 core that comes with the interface unit to the connector CN105 CN92 on the indoor control board in a room air conditioner Extending or severing the connecting cable 5 core from the interface unit causes malfunction Also keep the connecting cable 5 core as far as possible away from the power suppl...

Страница 7: ... SW502 and the rotary switches SW501 SW510 SW580 on the interface unit are not set cor rectly Replace the cable clamp according to the size of the connecting cable used for each system Fasten the cable tie as shown in the figure to prevent undesirable movement of the connecting cable 2 Connecting to the systems Mounting screw Connecting cable for each system Cable ties Cable clamp A1 B1 A2 B2 S A1...

Страница 8: ... remote controller Not necessary LE581 Orange When the lamp is illuminated power is supplied to the MA remote con troller from the Interface unit When the lamp is off power is not sup plied 5 Checking the communication status System controller Status signal output such as relay ME remote controller DC power source 12V TB530 TB571 TB520 Card key SYSTEM CONTROL Interface Coin timer CN591 MAC 333IF E...

Страница 9: ...roller LE501 Communication with MA remote controller LE502 OFF LE581 Power supply to MA remote controller Not available SW500 1 SW500 2 SW500 3 SW500 4 SW500 5 SW500 6 SW500 7 SW500 8 Set to OFF SW No Functions OFF Factory setting ON 12 VDC is output during operation in abnormal state etc 12 VDC is output when the air conditioner stops in normal state etc Continuous contact Instantaneous contact O...

Страница 10: ... m or more 2 core shield cable CVVS CPEVS MVVS size 1 25 mm2 or more Cable length a b The distance between the power supply unit and the furthest interface unit must be 200 m or less Note The system settings such as group setting on the system controller are required Refer to the instruction manual for the system controller used regarding the system settings such as group setting The number of ind...

Страница 11: ...ontroller or MA smart remote controller is used 2 core sheathed cable size 0 3 mm2 to 1 25 mm2 MA compact remote controller is used 2 core sheathed cable size 0 75 mm2 to 1 25 mm2 Cable length a The distance between the interface unit with refrigerant address of 0 and the MA remote controller must be 10 m or less Note Set the auto COOL HEAT display on the MA remote controller to OFF Refer to the i...

Страница 12: ...mum of 16 interface units can be connected to a MA remote controller In group operation all the air conditioners operate in the same operation status Operation status can not be set separately Connect one interface unit to each indoor unit connected to MXZ series outdoor unit Set separate refrigerant addresses to each unit Group operation cannot be performed with City Multi series If the interface...

Страница 13: ...h will open by insertion of the card key SW No Dip switch Operating details SW500 SW502 SW502 2 3 4 6 OFF SW502 5 ON SW500 6 8 OFF Cable type a Sheathed cable size 0 3 mm2 or more Specifications of communication cable Cable length a Cable size is 0 3 mm2 50 m or less Cable size is 0 5 mm2 100 m or less Note The operation of the paired remote controller prohibited by the card key is the ON OFF oper...

Страница 14: ...rtion of the card key SW No Dip switch Operating details SW500 SW500 6 8 OFF Cable type a Sheathed cable size 0 3 mm2 or more Specifications of communication cable Cable length a Cable size is 0 3 mm2 50 m or less Cable size is 0 5 mm2 100 m or less Note The operation of the paired remote controller prohibited by the card key is the ON OFF operation only Other operations such as setting the temper...

Страница 15: ...ifications of communication cable Cable length a Cable size is 0 3 mm2 50 m or less Cable size is 0 5 mm2 100 m or less Note The operation of the paired remote controller prohibited by the coin timer is the ON OFF operation only Other operations such as setting the temperature are enabled When the interface is connected to the M NET system even though the coin timer prohibits the manual operation ...

Страница 16: ...mm2 or more Note The operation of the paired remote controller prohibited by the coin timer is the ON OFF operation only Other operations such as setting the temperature are enabled When the interface is connected to the M NET system even though the coin timer prohibits the operation with the paired remote controller the ON OFF operation with the system controller is enabled When the interface is ...

Страница 17: ...nterface with the lowest M NET address or refrigerant address The wireless remote controller cannot be used together ON OFF SW No Dip switch SW No Dip switch SW No Dip switch Input change Change the input logic Operating details SW502 4 OFF It behaves as described in the Behavior section in this chart ON Switch 1 When it opens the air conditioner operates When it closes the air conditioner stops S...

Страница 18: ... Switch 2 is open opening Switch 1 operates the air conditioner When Switch 2 is open closing Switch 1 stops the air conditioner Switch 2 When Switch 2 opens the ON OFF operation with the paired remote controller and the M NET system controller is prohibited and the operation from Switch 1 is enabled When Switch 2 closes the ON OFF operation with the paired remote controller and the M NET system c...

Страница 19: ...ibited the state of the air conditioner does not change ON Switch 1 It behaves as described in the Behavior section in this chart Switch 2 When the ON OFF operation with the paired remote controller is prohibited the air conditioner stops Behavior setting when the manual operation prohibition is cancelled The air conditioner can be started to work when the operation prohibition is cancelled by the...

Страница 20: ...e sent by Switch 1 Switch 2 the paired remote controller and the M NET system controller Switch 1 Switch setting Settings for the input mode and the input change Set the state fixed operation using instantaneous contact switches SW No Dip switch Operating details SW502 SW502 2 4 ON SW502 3 OFF ON 1 2 3 4 5 6 7 8 OFF SW500 SW500 6 8 OFF Specifications of communication cable Cable type a Sheathed ca...

Страница 21: ...onnected to the M NET system if the system controller prohibits the manual ON OFF operation the ON OFF operation from the Switch 1 is prohibited When the interface is connected to the M NET system if the system controller prohibits the manual mode operation the HEAT COOL operation from Switch 2 is prohibited When the group setting is made with the M NET system or the MA remote controller connect S...

Страница 22: ...N when the air conditioner is off Relay 2 Relay 2 is OFF when the air conditioner operates abnormally Relay 2 is ON when the air conditioner operates normally Output settings Make settings for the outputs of ON OFF and normal abnormal SW No Dip switch Operating details SW500 SW500 4 5 8 OFF Specifications of communication cable Cable type a Sheathed cable Stranded cable size 0 3 mm2 to 1 25 mm2 Sh...

Страница 23: ...described in the Behavior section in this chart ON LED 1 LED 1 turns off when the air conditioner is on LED 1 is illuminated when the air conditioner is off LED 2 LED 2 turns off when the air conditioner operates abnormally LED 2 is illuminated when the air conditioner operates normally Specifications of communication cable Cable type a Sheathed cable Stranded cable size 0 3 mm2 to 1 25 mm2 Sheath...

Страница 24: ...output and the control signal output Behavior Switch setting Specifications of communication cable Note Relay 1 2 Coil rating 12 VDC 75 mA or less Relay 1 Relay 2 Output change Change the output logic SW No Dip switch Operating details SW502 OFF It behaves as described in the Behavior section in this chart ON Relay 1 Relay 1 is OFF when the air conditioner is on Relay 1 is ON when the air conditio...

Страница 25: ...n cable Note Relay 1 2 Coil rating 12 VDC 75 mA or less Relay 1 Relay 2 Output change Change the output logic SW No Dip switch Operating details SW502 OFF It behaves as described in the Behavior section in this chart ON Relay 1 Relay 1 is OFF when the air conditioner is on Relay 1 is ON when the air conditioner is off Relay 2 Relay 2 is OFF when the conditions to operate the external humidifier ar...

Страница 26: ...ntrol ON OFF signal of the external heater and the external humidifier can be output to the relay Relay 1 Relay 1 is ON when the conditions to operate the external heater are satisfied Relay1 remains ON until the conditions for OFF are satisfied Conditions to operate the heater The air conditioner is operating in the heating or the automatic heating mode and the room temperature is 2 5 C 4 5 F or ...

Страница 27: ...ner turns on by its main power source being turned on Switch setting Note The ON OFF control by main power source is disabled when an indoor unit is connected to the MXZ series outdoor unit Set up the system to prevent two or more room air conditioners from recovering simultaneously when starting the air conditioners using the ON OFF control by main power source To avoid inrush current start the o...

Страница 28: ... the timer is set with the wireless remote controller the MA remote controller the ME remote controller or the system controller will not show the timer display The timer set with the MA remote controller the ME remote controller or the system controller will not be cancelled with the wireless remote controller 3 Manual operation prohibition When the manual operation ON OFF set temperature or oper...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...p 2012 Specifications are subject to change without notice Issued in Sep 2012 M R0598 SIZ1209 MEE HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN SYSTEM CONTROL INTERFACE Model MAC 333IF E TECHNICAL MANUAL ...

Отзывы: