MAC-333IF-E

(4) Coin timer connection (Switch will open after a coin is inserted.)

Switch will open after insertion of a coin, which starts/stops the room air conditioner.

Function
summary
System
configuration

Behavior

· When a coin is inserted (and the switch opens), the air conditioner starts and the ON/OFF operation from the paired remote controller
  is enabled.
· When the timer expires (and the switch closes), the air conditioner stops and the ON/OFF operation from the paired remote controller
  is prohibited.
 * “Paired remote controller” includes the wireless remote controller that comes with the room air conditioner, the MA remote controller,
    and the ME remote controller.

· Coin timer connection (Switch will open after insertion of a coin.)

SW No.

Dip switch

Operating details

· SW502-2,3,4: OFF
· SW502-5,6: ON

· Cable length

 a: Cable size is 0.3 mm

2

: 50 m or less / Cable size is 0.5 mm

2

: 100 m or less

Specifications
of communication 
cable

· Cable type

a: Sheathed cable, size 0.3 mm

2

 or more

Note

· The operation of the paired remote controller prohibited by the coin timer is the ON/OFF operation only. 
  Other operations, such as setting the temperature, are enabled.
· When the interface is connected to the M-NET system, even though the coin timer prohibits the operation with the paired remote
  controller, the ON/OFF operation with the system controller is enabled. 
· When the interface is connected to the M-NET system, if the system controller prohibits the manual ON/OFF operation, the ON/OFF

operation with the coin timer is prohibited. To enable the coin timer, do not disable the manual operation on the system controller.

· When the group setting is made with the M-NET system or the MA remote controller, connect the coin timer to the interface with the 
  lowest M-NET address or refrigerant address. The wireless remote controller cannot be used together.

SW502

ON

1

2

3

4

5

6

7

8

OFF

· SW500-6,8: OFF

SW500

ON

1

2

3

4

5

6

7

8

OFF

Brown

Red

Orange

Switch setting

MAC333IF-E

CN591

3

2

1

Insulate here.

Coin timer must be the one that
· opens the switch when inserted.
· can be used on the following condition:
  12 VDC, 0.5 to 2.0 mA

a

SYSTEM CONTROL Interface

Содержание MAC-333IF-E

Страница 1: ...2012 SYSTEM CONTROL INTERFACE Model MAC 333IF E TECHNICAL MANUAL ...

Страница 2: ...B ...

Страница 3: ...2 2 INSTALLATION OF INTERFACE UNIT 4 3 CONNECTION 4 4 SETTING OF DIP SWITCH AND ROTARY SWITCH 7 5 FUNCTIONS 8 5 1 M NET CONNECTION 8 5 2 MA REMOTE CONTROLLER CONNECTION 9 5 3 REMOTE CONTROL 11 5 4 STATUS SIGNAL OUTPUT 20 5 5 ON OFF CONTROL BY MAIN POWER SOURCE 25 6 IMPORTANT NOTE 26 ...

Страница 4: ...normal signals ON OFF control by main power source Turning M series on when the main power is turned on S series Indoor unit s connected to SUZ or MXZ series The following table shows the restrictions on the combination use of the functions ON OFF control by main power source can be used regardless of the following combinations however ON OFF control by main power source cannot be used with AUTO r...

Страница 5: ...mmunication with connected equipment For details refer to 3 5 Checking the communication status in this manual Function setting switch B For details refer to 4 SETTING OF DIP SWITCHAND ROTARY SWITCH in this manual Function setting switch A For details refer to 4 SETTING OF DIP SWITCHAND ROTARY SWITCH in this manual LED for checking communica tion with connected equipment For details refer to 3 5 C...

Страница 6: ...the following procedures turn off the main power to the air conditioner Connect the connecting cable 5 core that comes with the interface unit to the connector CN105 CN92 on the indoor control board in a room air conditioner Extending or severing the connecting cable 5 core from the interface unit causes malfunction Also keep the connecting cable 5 core as far as possible away from the power suppl...

Страница 7: ... SW502 and the rotary switches SW501 SW510 SW580 on the interface unit are not set cor rectly Replace the cable clamp according to the size of the connecting cable used for each system Fasten the cable tie as shown in the figure to prevent undesirable movement of the connecting cable 2 Connecting to the systems Mounting screw Connecting cable for each system Cable ties Cable clamp A1 B1 A2 B2 S A1...

Страница 8: ... remote controller Not necessary LE581 Orange When the lamp is illuminated power is supplied to the MA remote con troller from the Interface unit When the lamp is off power is not sup plied 5 Checking the communication status System controller Status signal output such as relay ME remote controller DC power source 12V TB530 TB571 TB520 Card key SYSTEM CONTROL Interface Coin timer CN591 MAC 333IF E...

Страница 9: ...roller LE501 Communication with MA remote controller LE502 OFF LE581 Power supply to MA remote controller Not available SW500 1 SW500 2 SW500 3 SW500 4 SW500 5 SW500 6 SW500 7 SW500 8 Set to OFF SW No Functions OFF Factory setting ON 12 VDC is output during operation in abnormal state etc 12 VDC is output when the air conditioner stops in normal state etc Continuous contact Instantaneous contact O...

Страница 10: ... m or more 2 core shield cable CVVS CPEVS MVVS size 1 25 mm2 or more Cable length a b The distance between the power supply unit and the furthest interface unit must be 200 m or less Note The system settings such as group setting on the system controller are required Refer to the instruction manual for the system controller used regarding the system settings such as group setting The number of ind...

Страница 11: ...ontroller or MA smart remote controller is used 2 core sheathed cable size 0 3 mm2 to 1 25 mm2 MA compact remote controller is used 2 core sheathed cable size 0 75 mm2 to 1 25 mm2 Cable length a The distance between the interface unit with refrigerant address of 0 and the MA remote controller must be 10 m or less Note Set the auto COOL HEAT display on the MA remote controller to OFF Refer to the i...

Страница 12: ...mum of 16 interface units can be connected to a MA remote controller In group operation all the air conditioners operate in the same operation status Operation status can not be set separately Connect one interface unit to each indoor unit connected to MXZ series outdoor unit Set separate refrigerant addresses to each unit Group operation cannot be performed with City Multi series If the interface...

Страница 13: ...h will open by insertion of the card key SW No Dip switch Operating details SW500 SW502 SW502 2 3 4 6 OFF SW502 5 ON SW500 6 8 OFF Cable type a Sheathed cable size 0 3 mm2 or more Specifications of communication cable Cable length a Cable size is 0 3 mm2 50 m or less Cable size is 0 5 mm2 100 m or less Note The operation of the paired remote controller prohibited by the card key is the ON OFF oper...

Страница 14: ...rtion of the card key SW No Dip switch Operating details SW500 SW500 6 8 OFF Cable type a Sheathed cable size 0 3 mm2 or more Specifications of communication cable Cable length a Cable size is 0 3 mm2 50 m or less Cable size is 0 5 mm2 100 m or less Note The operation of the paired remote controller prohibited by the card key is the ON OFF operation only Other operations such as setting the temper...

Страница 15: ...ifications of communication cable Cable length a Cable size is 0 3 mm2 50 m or less Cable size is 0 5 mm2 100 m or less Note The operation of the paired remote controller prohibited by the coin timer is the ON OFF operation only Other operations such as setting the temperature are enabled When the interface is connected to the M NET system even though the coin timer prohibits the manual operation ...

Страница 16: ...mm2 or more Note The operation of the paired remote controller prohibited by the coin timer is the ON OFF operation only Other operations such as setting the temperature are enabled When the interface is connected to the M NET system even though the coin timer prohibits the operation with the paired remote controller the ON OFF operation with the system controller is enabled When the interface is ...

Страница 17: ...nterface with the lowest M NET address or refrigerant address The wireless remote controller cannot be used together ON OFF SW No Dip switch SW No Dip switch SW No Dip switch Input change Change the input logic Operating details SW502 4 OFF It behaves as described in the Behavior section in this chart ON Switch 1 When it opens the air conditioner operates When it closes the air conditioner stops S...

Страница 18: ... Switch 2 is open opening Switch 1 operates the air conditioner When Switch 2 is open closing Switch 1 stops the air conditioner Switch 2 When Switch 2 opens the ON OFF operation with the paired remote controller and the M NET system controller is prohibited and the operation from Switch 1 is enabled When Switch 2 closes the ON OFF operation with the paired remote controller and the M NET system c...

Страница 19: ...ibited the state of the air conditioner does not change ON Switch 1 It behaves as described in the Behavior section in this chart Switch 2 When the ON OFF operation with the paired remote controller is prohibited the air conditioner stops Behavior setting when the manual operation prohibition is cancelled The air conditioner can be started to work when the operation prohibition is cancelled by the...

Страница 20: ...e sent by Switch 1 Switch 2 the paired remote controller and the M NET system controller Switch 1 Switch setting Settings for the input mode and the input change Set the state fixed operation using instantaneous contact switches SW No Dip switch Operating details SW502 SW502 2 4 ON SW502 3 OFF ON 1 2 3 4 5 6 7 8 OFF SW500 SW500 6 8 OFF Specifications of communication cable Cable type a Sheathed ca...

Страница 21: ...onnected to the M NET system if the system controller prohibits the manual ON OFF operation the ON OFF operation from the Switch 1 is prohibited When the interface is connected to the M NET system if the system controller prohibits the manual mode operation the HEAT COOL operation from Switch 2 is prohibited When the group setting is made with the M NET system or the MA remote controller connect S...

Страница 22: ...N when the air conditioner is off Relay 2 Relay 2 is OFF when the air conditioner operates abnormally Relay 2 is ON when the air conditioner operates normally Output settings Make settings for the outputs of ON OFF and normal abnormal SW No Dip switch Operating details SW500 SW500 4 5 8 OFF Specifications of communication cable Cable type a Sheathed cable Stranded cable size 0 3 mm2 to 1 25 mm2 Sh...

Страница 23: ...described in the Behavior section in this chart ON LED 1 LED 1 turns off when the air conditioner is on LED 1 is illuminated when the air conditioner is off LED 2 LED 2 turns off when the air conditioner operates abnormally LED 2 is illuminated when the air conditioner operates normally Specifications of communication cable Cable type a Sheathed cable Stranded cable size 0 3 mm2 to 1 25 mm2 Sheath...

Страница 24: ...output and the control signal output Behavior Switch setting Specifications of communication cable Note Relay 1 2 Coil rating 12 VDC 75 mA or less Relay 1 Relay 2 Output change Change the output logic SW No Dip switch Operating details SW502 OFF It behaves as described in the Behavior section in this chart ON Relay 1 Relay 1 is OFF when the air conditioner is on Relay 1 is ON when the air conditio...

Страница 25: ...n cable Note Relay 1 2 Coil rating 12 VDC 75 mA or less Relay 1 Relay 2 Output change Change the output logic SW No Dip switch Operating details SW502 OFF It behaves as described in the Behavior section in this chart ON Relay 1 Relay 1 is OFF when the air conditioner is on Relay 1 is ON when the air conditioner is off Relay 2 Relay 2 is OFF when the conditions to operate the external humidifier ar...

Страница 26: ...ntrol ON OFF signal of the external heater and the external humidifier can be output to the relay Relay 1 Relay 1 is ON when the conditions to operate the external heater are satisfied Relay1 remains ON until the conditions for OFF are satisfied Conditions to operate the heater The air conditioner is operating in the heating or the automatic heating mode and the room temperature is 2 5 C 4 5 F or ...

Страница 27: ...ner turns on by its main power source being turned on Switch setting Note The ON OFF control by main power source is disabled when an indoor unit is connected to the MXZ series outdoor unit Set up the system to prevent two or more room air conditioners from recovering simultaneously when starting the air conditioners using the ON OFF control by main power source To avoid inrush current start the o...

Страница 28: ... the timer is set with the wireless remote controller the MA remote controller the ME remote controller or the system controller will not show the timer display The timer set with the MA remote controller the ME remote controller or the system controller will not be cancelled with the wireless remote controller 3 Manual operation prohibition When the manual operation ON OFF set temperature or oper...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...p 2012 Specifications are subject to change without notice Issued in Sep 2012 M R0598 SIZ1209 MEE HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN SYSTEM CONTROL INTERFACE Model MAC 333IF E TECHNICAL MANUAL ...

Отзывы: