14
MAC-333IF-E
(4) Coin timer connection (Switch will open after a coin is inserted.)
Switch will open after insertion of a coin, which starts/stops the room air conditioner.
Function
summary
System
configuration
Behavior
· When a coin is inserted (and the switch opens), the air conditioner starts and the ON/OFF operation from the paired remote controller
is enabled.
· When the timer expires (and the switch closes), the air conditioner stops and the ON/OFF operation from the paired remote controller
is prohibited.
* “Paired remote controller” includes the wireless remote controller that comes with the room air conditioner, the MA remote controller,
and the ME remote controller.
· Coin timer connection (Switch will open after insertion of a coin.)
SW No.
Dip switch
Operating details
· SW502-2,3,4: OFF
· SW502-5,6: ON
· Cable length
a: Cable size is 0.3 mm
2
: 50 m or less / Cable size is 0.5 mm
2
: 100 m or less
Specifications
of communication
cable
· Cable type
a: Sheathed cable, size 0.3 mm
2
or more
Note
· The operation of the paired remote controller prohibited by the coin timer is the ON/OFF operation only.
Other operations, such as setting the temperature, are enabled.
· When the interface is connected to the M-NET system, even though the coin timer prohibits the operation with the paired remote
controller, the ON/OFF operation with the system controller is enabled.
· When the interface is connected to the M-NET system, if the system controller prohibits the manual ON/OFF operation, the ON/OFF
operation with the coin timer is prohibited. To enable the coin timer, do not disable the manual operation on the system controller.
· When the group setting is made with the M-NET system or the MA remote controller, connect the coin timer to the interface with the
lowest M-NET address or refrigerant address. The wireless remote controller cannot be used together.
SW502
ON
1
2
3
4
5
6
7
8
OFF
· SW500-6,8: OFF
SW500
ON
1
2
3
4
5
6
7
8
OFF
Brown
Red
Orange
Switch setting
MAC333IF-E
CN591
3
2
1
Insulate here.
Coin timer must be the one that
· opens the switch when inserted.
· can be used on the following condition:
12 VDC, 0.5 to 2.0 mA
a
SYSTEM CONTROL Interface