20
MAC-333IF-E
5.4 STATUS SIGNAL OUTPUT
(1) Relay outputs of ON/OFF operation signal and normal/abnormal signal
Function
summary
ON/OFF signal and normal/abnormal signal of the room air conditioner can be output to the relay.
System
configuration
MAC333IF-E
C
R1
TB571
R2
TB530
DC power
source
12 V
DC power source
12 VDC (+10 %, -0 %), 5 W or more
a
b
SYSTEM CONTROL interface
* External power source is required for the status output.
Behavior
·
Relay 1
· Relay 1 is ON when the air conditioner is on.
· Relay 1 is OFF when the air conditioner is off.
·
Relay 2
· Relay 2 is ON when the air conditioner operates abnormally.
· Relay 2 is OFF when the air conditioner operates normally.
Switch setting
·
Output change
Change the output logic.
SW No.
Dip switch
Operating details
SW502-1
· OFF
:
· It behaves as described in the “Behavior” section in this chart
· ON:
·
Relay 1
· Relay 1 is OFF when the air conditioner is on.
· Relay 1 is ON when the air conditioner is off.
·
Relay 2
· Relay 2 is OFF when the air conditioner operates abnormally.
· Relay 2 is ON when the air conditioner operates normally.
·
Output settings
Make settings for the outputs of ON/OFF and normal/abnormal.
SW No.
Dip switch
Operating details
SW500
· SW500-4,5,8: OFF
Specifications
of communication
cable
·
Cable type
· a: Sheathed cable (Stranded cable), size 0.3 mm
2
to 1.25 mm
2
/ Sheathed cable (Solid cable), ø0.4 mm to ø1.2 mm
· b: Use the cable specified for the external power source. Its size must be from 0.3 mm
2
to 1.25 mm
2
.
·
Cable length
· a: Cable size is 0.3 mm
2
: 50 m or less / Cable size is 0.5 mm
2
: 100 m or less
· b: Follow the requirement for the external power source.
Note
· External power source is required for the status output.
· TB530 and TB571 have polarities, so check them before connection.
· Do not connect DC power source to TB571.
· When a relay with a built-in diode is used, take care to choose the correct polarity.
TB571 C: + potential
TB571 R1 and R2: - potential
Relay 1, 2
Coil rating: 12 VDC, 75 mA or less
Relay 1
Relay 2
ON
1
2
3
4
5
6
7
8
OFF
ON
OFF
ON
1
2
3
4
5
6
7
8
OFF
Содержание MAC-333IF-E
Страница 1: ...2012 SYSTEM CONTROL INTERFACE Model MAC 333IF E TECHNICAL MANUAL ...
Страница 2: ...B ...
Страница 29: ......
Страница 30: ......
Страница 31: ......