A.1.1
PLC Status Diagnostic Information (M8000 to M8009)
A.1.2
Clock Devices and Real Time Clock (M8011 to M8019)
Special Relays
Appendix
A - 2
MITSUBISHI ELECTRIC
RUN state
M8004
M8000
M8001
M8002
M8003
1 scan time
Special Relay
Read
Write
CPU
Function
M8000
쏹
—
FX
1S
FX
1N
FX
2N
FX
2NC
FX
3G
FX
3U
FX
3UC
RUN monitor
(NO contact)
M8001
쏹
—
RUN monitor
(NC contact)
M8002
쏹
—
Initial pulse
(NO contact)
M8003
쏹
—
Initial pulse
(NC contact)
M8004
쏹
—
Error occurrence
M8005
쏹
—
FX
2N
FX
2NC
FX
3G
FX
3U
FX
3UC
Battery voltage low (ON when battery voltage is below the
value set in D8006)
M8006
쏹
—
Battery error latch (M8006 is set when battery voltage low is
detected)
M8007
쏹
—
FX
2N
FX
2NC
FX
3U
FX
3UC
Momentary power failure
M8008
쏹
—
Power failure detected
M8009
쏹
—
FX
2N
FX
2NC
FX
3G
FX
3U
FX
3UC
24V DC down (service power supply)
Special Relay
Read
Write
CPU
Function
M8010
—
—
—
Not used
M8011
쏹
—
FX
1S
FX
1N
FX
2N
FX
2NC
FX
3G
FX
3U
FX
3UC
10 ms clock pulse
ON and OFF in 10 ms cycle (ON: 5 ms, OFF: 5 ms)
M8012
쏹
—
100 ms clock pulse
ON and OFF in 100 ms cycle (ON: 50 ms, OFF: 50 ms)
M8013
쏹
—
1 s clock pulse
ON and OFF in 1 s cycle (ON: 500 ms, OFF: 500 ms)
M8014
쏹
—
1 min clock pulse
ON and OFF in 1 min cycle (ON: 30 s, OFF: 30 s)
M8015
쏹
쏹
Clock stop and preset (For real time clock)
M8016
쏹
—
Time read display is stopped (For real time clock)
The contents of D8013 to D8019 is frozen, but the clock is
still running.
M8017
쏹
쏹
±30 seconds correction (For real time clock)
M8018
쏹
—
Real time clock installation detection (Always ON)
For an FX
2NC
a memory card with integrated RTC must be
installed.
M8019
쏹
—
Real time clock (RTC) setting error
Содержание FX2N-32CAN
Страница 1: ...MITSUBISHI ELECTRIC FACTORY AUTOMATION Programmable Logic Controllers GX IEC Developer ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ...IV MITSUBISHI ELECTRIC ...
Страница 18: ...Modular PLC Training Hardware Course Overview and Requirements 1 2 MITSUBISHI ELECTRIC ...
Страница 172: ...Monitoring Instances of Function Blocks Advanced Monitoring Functions 7 12 MITSUBISHI ELECTRIC ...
Страница 176: ...Device Edit 8 4 MITSUBISHI ELECTRIC ...
Страница 190: ...Assigning DUT Variables to Function Blocks Data Unit Types DUT 10 10 MITSUBISHI ELECTRIC ...
Страница 198: ...Array Example Single Dimension Array Arrays 11 8 MITSUBISHI ELECTRIC ...
Страница 219: ...Sequential Function Chart SFC SFC Elements Training Manual GX IEC Developer 14 3 ...
Страница 220: ...14 3 SFC configuration examples SFC configuration examples Sequential Function Chart SFC 14 4 MITSUBISHI ELECTRIC ...
Страница 230: ...Structured Text Program Example IEC Structured Text 16 4 MITSUBISHI ELECTRIC ...
Страница 248: ...Configuring GX IEC Developer to access the PLC on Ethernet Ethernet Communications 18 10 MITSUBISHI ELECTRIC ...
Страница 278: ...PLC Components Glossary Appendix A 18 MITSUBISHI ELECTRIC ...
Страница 283: ......