PARAMETERS
105
Pr. 79 "operation mode selection"
Related parameters
<Setting>
Pr. 77
Setting
Function
0
Parameter values may only be written during a stop in the
PU operation mode. (Note 1)
1
Write disabled.
Values of Pr. 22, Pr. 75, Pr. 77 and Pr. 79 "operation
mode selection" can be written.
2
Write enabled even during operation.
Note: 1. The parameters half-tone screened in the parameter list can be set at any
time.
2. If Pr. 77 = "2", the values of Pr. 23, Pr. 66, Pr. 71, Pr. 79, Pr. 80, Pr. 83,
Pr. 84, Pr. 96, Pr. 180 to Pr. 183 and Pr. 190 to Pr. 192 cannot be written
during operation. Stop operation when changing their parameter settings.
3. By setting "1" in Pr. 77, the following clear operations can be inhibited:
!
Parameter clear
!
All clear
4.2.32 Reverse rotation prevention selection (Pr. 78)
Pr. 78 "reverse rotation prevention
selection"
This function can prevent any reverse rotation fault resulting from the incorrect input of
the start signal.
!
Used for a machine which runs only in one direction, e.g. fan, pump.
(The setting of this function is valid for the combined, PU, external and
communication operations.)
Parameter
Number
Factory
Setting
Setting
Range
78
0
0, 1, 2
<Setting>
Pr. 78 Setting
Function
0
Both forward and reverse
rotations allowed
1
Reverse rotation disallowed
2
Forward rotation disallowed
4