![Mitsubishi Electric FR-E 520S EC Скачать руководство пользователя страница 101](http://html.mh-extra.com/html/mitsubishi-electric/fr-e-520s-ec/fr-e-520s-ec_instruction-manual_239223101.webp)
PARAMETERS
86
Pr. 73 "0-5V/0-10V selection"
Pr. 79 "operation mode selection"
Pr. 254 "analog polarity reversible
lower limit"
Pr. 902 "frequency setting voltage bias"
Pr. 903 "frequency setting voltage gain"
Related parameters
"
"
Frequency at 5V (10V) input (Pr. 38)
4.2.16 Frequency at 5V (10V) input (Pr. 38)
Pr. 38 "frequency at 5V (10V) input"
!
You can set the frequency
provided when the
frequency setting signal
from the potentiometer
connected across terminals
2-5 (frequency setting
potentiometer) is 5VDC (or
10VDC).
5V(10V)
fm1
Pr.38
fm2
O
u
tput
f
re
quenc
y
(Hz
)
Output frequency
range
Frequency setting signal
Parameter
Number
Factory Setting
Setting Range
38
50Hz
1 to 400Hz
4.2.17 Frequency at 20mA input (Pr. 39)
"
Frequency at 20mA input (Pr. 39)
Pr. 39 "frequency at 20mA input"
!
You can set the frequency
provided when the
frequency setting signal
input across terminals 4-5 is
20mA.
20mA
fm1
Pr.39
fm2
O
u
tput
fr
equen
c
y
(H
z)
Output frequency
range
Frequency setting signal
Parameter
Number
Factory Setting
Setting Range
39
50Hz
1 to 400Hz
Pr. 79 "operation mode selection"
Pr. 904 "frequency setting current bias"
Pr. 905 "frequency setting current gain"
Related parameters