![Mitsubishi Electric FR-E 520S EC Скачать руководство пользователя страница 87](http://html.mh-extra.com/html/mitsubishi-electric/fr-e-520s-ec/fr-e-520s-ec_instruction-manual_239223087.webp)
PARAMETERS
72
"
"
Multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)
4.2.4 Multi-speed operation
(Pr. 4, Pr. 5, Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)
Pr. 4 "multi-speed setting (high speed)"
Pr. 5 "multi-speed setting (middle speed)"
Pr. 6 "multi-speed setting (low speed)"
Pr. 24 to Pr. 27 "multi-speed setting
(speeds 4 to 7)"
Pr. 232 to Pr. 239 "multi-speed setting
(speeds 8 to 15)"
Used to switch between the predetermined running
speeds.
"
Any speed can be selected by merely switching on/off the corresponding contact
signals (RH, RM, RL, REX signals).
"
By using these functions with Pr. 1 "maximum frequency" and Pr. 2 "minimum
frequency", up to 17 speeds can be set.
"
Valid in the external operation mode or combined mode (Pr. 79
=
4).
Parameter Number
Factory Setting
Setting Range
Remarks
4
50Hz
0 to 400Hz
5
30Hz
0 to 400Hz
6
10Hz
0 to 400Hz
24 to 27
9999
0 to 400Hz, 9999
9999: Not selected
232 to 239
9999
0 to 400Hz, 9999
9999: Not selected
Time
RH
RM
RL
Speed 1
(high speed)
Speed 2
(middle speed)
Speed 5
Speed 6
Speed 7
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
O
u
tp
ut
fre
que
nc
y(H
z
)
Speed 3
(low speed)
Speed 4
O
u
tp
ut
fre
que
nc
y(
H
z
)
Speed 8
Speed 9
Speed 10
Speed 11
Speed 12
Speed 13
Speed 14
Speed 15
Time
RH
RM
RL
REX
ON ON ON ON ON ON
ON
ON
ON
ON
ON
ON ON
ON ON
ON ON ON ON
ON
<Setting>
!
Set the running frequencies in the corresponding parameters.
!
Each speed (frequency) can be set as desired between 0 and 400Hz during inverter
operation.
After the required multi-speed setting parameter has been read, the setting can be
changed by pressing the
/
key. In this case, when you release the
/
key, press the
SET
key (
WRITE
key when using the parameter unit (FR-PU04)) to store
the set frequency.
!
Use any of Pr. 180 to Pr. 183 to assign the terminal used to input the REX signal.
Pr. 1 "maximum frequency"
Pr. 2 "minimum frequency"
Pr. 29 "acceleration/deceleration
pattern"
Pr. 79 "operation mode
selection"
Pr. 180 to Pr. 183 (input terminal
function selection)
Related parameters