PARAMETERS
122
<Setting>
To make communication between the personal computer and inverter, the
communication specifications must be set to the inverter initially. If initial setting is not
made or there is a setting fault, data transfer cannot be made.
Note:
After making the initial setting of the parameters, always reset the inverter.
After you have changed the communication-related parameters,
communication cannot be made unit the inverter is reset.
Parameter
Number
Definition
Setting
Description
117
Station
number
0 to 31
Station number specified for communication from the
PU connector.
Set the inverter station numbers when two or more
inverters are connected to one personal computer.
48
4800 bps
96
9600 bps
118
Communica-
tion speed
192
19200 bps
0
Stop bit length 1 bit
1
Communication operation
Stop bit length 2 bits
100
Stop bit length 1 bit
8 data
bits
101
Communication operation
(NET mode communication) Stop bit length 2 bits
10
Stop bit length 1 bit
11
Communication operation
Stop bit length 2 bits
110
Stop bit length 1 bit
119*1
Stop bit
length
7 bits
111
Communication operation
(NET mode communication) Stop bit length 2 bits
0
Absent
1
Odd parity present
120
Parity check
presence/
absence
2
Even parity present
0 to 10
Set the permissible number of retries at occurrence of
a data receive error.
If the number of consecutive errors exceeds the
permissible value, the inverter will come to an alarm
stop.
121
Number of
communica-
tion retries
9999
(65535)
If a communication error occurs, the inverter will not
come to an alarm stop. At this time, the inverter can
be coasted to a stop by MRS or RESET input.
During a communication error (H0 to H5), the minor
fault signal (LF) is switched on. Allocate the used
terminal with any of Pr. 190 to Pr. 192 (multi-function
outputs).
0
No communication
0.1 to 999.8
Set the communication check time [seconds] interval.
If a no-communication state persists for longer than
the permissible time, the inverter will come to an
alarm stop.
122
Communica-
tion check
time interval
9999
Communication check suspension
0 to 150
Set the waiting time between data transmission to the
inverter and response.
123
Waiting time
setting
9999
Set with communication data.