![Mitsubishi Electric FR-E 520S EC Скачать руководство пользователя страница 77](http://html.mh-extra.com/html/mitsubishi-electric/fr-e-520s-ec/fr-e-520s-ec_instruction-manual_239223077.webp)
PARAMETERS
62
Func-
tion
Para-
meter
Number
Name
Setting
Range
Minimum
Setting
Increments
Factory
Setting
Refer
To:
Custo-
mer
Setting
60
Shortest acceleration/
deceleration mode
0, 1, 2, 11,
12
1
0
95
61
Reference I for intelligent
mode
0 to 500A,
9999
0.01A
9999
95
62
Ref. I for intelligent mode
accel
0 to 200%,
9999
1%
9999
95
63
Ref. I for intelligent mode
decel
0 to 200%,
9999
1%
9999
95
65
Retry selection
0, 1, 2, 3
1
0
96
66
Stall prevention operation
level reduction starting
frequency (Note 6)
0 to 400Hz
0.01Hz
(Note 3)
50Hz
80
67
Number of retries at alarm
occurrence
0 to 10,
101 to 110
1
0
96
68
Retry waiting time
0.1 to 360 s
0.1 s
1 s
96
69
Retry count display erasure
0
1
0
96
70
Special regenerative brake
duty
0 to 30%
0.1%
0%
83
71
Applied motor (Note 6)
0, 1, 3, 5, 6,
13, 15, 16,
23, 100,
101,103,
105, 106,
113, 115,
116,123
1
0
98
72
PWM frequency selection
0 to 15
1
1
99
73
0-5V/0-10V selection
0, 1, 10, 11
(Note 9)
1
0
100
74
Filter time constant
0 to 8
1
1
102
75
Reset selection/
disconnected PU detection/
PU stop selection
0 to 3,
14 to 17
1
14
102
77
Parameter write disable
selection
0, 1, 2
1
0
104
78
Reverse rotation prevention
selection
0, 1, 2
1
0
105
O
perat
ion select
ion f
unct
ions
79
Operation mode selection
(Note 6)
0 to 4,6 to 8
1
0
106
80
Motor capacity (Note 6)
0.2 to 7.5kW,
9999
0.01kW
9999
110
82
Motor exciting current
0 to 500A,
9999
0.01A
9999
111
83
Rated motor voltage (Note 6) 0 to 1000V
0.1V
200V/
400V
111
84
Rated motor frequency
(Note 6)
50 to 120Hz
0.01Hz
(Note 3)
50Hz
111
90
Motor constant (R1)
0 to 50
Ω
,
9999
0.001
Ω
9999
111
G
eneral-purpose m
agnet
ic
fl
ux v
e
ct
or cont
rol
96
Auto-tuning setting/status
(Note 6)
0, 1
1
0
111
Parameter L