Appendix 2 When using the communication option.
196
Appendix 2 When using the communicaton option.
The extended functions for E.OPT error and E. 3 error have been added to this
instruction manual. (Pr. 500 to Pr. 502)
(1) Pr. 500 "communication error execution waiting time"
You can set the waiting time from occurrence of a communication line fault to
communication error indication "E.OPT".
Parameter
Number
Setting Range
Minimum Setting
Increment
Factory Setting
500
0 to 999.8 s
0.1 s
0
Communication line status
Normal
Abnormal
Communication error "E.OPT"
Indication output
Time set in Pr. 500
If a communication line fault still persists after the time set in Pr. 500 has elapsed, it is
recognized as a communication error and the communication error indication "E.OPT"
is output.
If communication is restored to normal during the set time, operation is continued
without a communication error indication.
(2) Pr. 501 "communication error occurrence count indication"
You can display the cumulative number of communication line faults that occurred.
Write "0" to Pr. 501 to clear the communication error occurrence count.
Parameter
Number
Setting Range
Minimum Setting
Increment
Factory Setting
501
0
1
0
Count timing according to
communication line status
Normal
Ab-
normal
Normal
Abnormal
1 count
1 count
At the time when a communication line fault occurs, one count is made in Pr. 501
"communication error occurrence count indication".
Note: The communication error occurrence count indication is temporarily stored in
RAM.
As it is reflected to E
2
PROM per hour only, performing power-on reset or
inverter reset causes the last value stored in E
2
PROM to appear in the
parameter.