Electro-magnetic interference (EMI) and leakage currents
PRECAUTIONS FOR USE OF THE CONVERTER UNIT
65
3
3.1.3
Built-in EMC filter
The converter unit is equipped with a built-in EMC filter (capacitive filter).
The filter is effective in reducing air-propagated noise on the input side of the converter unit.
Two EMC filter ON/OFF connectors are provided. Both connectors are initially set to the "disabled" (OFF) position.
To enable the EMC filters, fit both of the EMC filter ON/OFF connectors to the "enabled" (ON) position.
<Switching ON/OFF the filter>
• Before removing a front cover, check to make sure that the indication of the inverter operation panel is OFF, wait for at least
10 minutes after the power supply has been switched OFF, and check that there is no residual voltage using a tester or the
like.
• When disconnecting the connector, push the fixing tab and pull the connector straight without pulling the cable or forcibly
pulling the connector with the tab fixed.
When installing the connector, also engage the fixing tab securely.
(If it is difficult to disconnect the connector, use a pair of needle-nose pliers, etc.)
NOTE
• Fit the connector to either ON or OFF position.
• Enabling (turning ON) the EMC filter increases leakage current. (Refer to
WARNING
While power is ON, do not open the front cover. Otherwise you may get an electric shock.
EMC filter OFF
EMC filter ON
FILTER
OFF
ON
FILTER
OFF
ON
FIL
TER
OFF ON
FIL
TER
OFF ON
EMC filter OFF
EMC filter ON
EMC filter ON/OFF connector
EMC filter ON/OFF connector
EMC filter
ON/OFF connector
(Side view)
Disengage connector fixing tab
With tab disengaged,
pull up the connector straight.