Peripheral devices
17
2
NOTE
• When the converter unit capacity is larger than the motor capacity, select an MCCB and an MC (magnetic contactor)
according to the converter unit model, and select cables and reactors according to the motor output.
• When the breaker on the converter unit's input side trips, check for the wiring fault (short circuit), damage to internal parts of
the inverter or the converter unit, etc. The cause of the trip must be identified and removed before turning ON the power of
the breaker.
• When the inverter is operated while the power distribution control equipment connected between the delta wiring of the
transformer and terminals R2/L12, S2/L22, and T2/L32 is OFF, the converter unit may be damaged.
Содержание FR-CC2-P
Страница 59: ...MEMO 58 ...
Страница 73: ...MEMO 72 ...
Страница 137: ...MEMO 136 ...
Страница 153: ...MEMO 152 ...
Страница 165: ...MEMO 164 ...
Страница 169: ...MEMO 168 ...