Control circuit
49
2
Signal inputs by contactless switches
The contact input terminals of the converter unit (RES, OH, RDI) can be controlled using a transistor instead of a contact
switch as shown below.
2.7.4
Wiring precautions
• It is recommended to use a cable of 0.75 mm
2
for connection to the control circuit terminals.
• The wiring length should be 30 m at the maximum.
• Use two or more parallel micro-signal contacts or twin contacts to prevent
contact faults when using contact inputs since the control circuit input signals
are micro-currents.
• To suppress EMI, use shielded or twisted cables for the control circuit
terminals and run them away from the main and power circuits (including the
200 V relay sequence circuit). For the cables connected to the control circuit terminals, connect their shields to the common
terminal of the connected control circuit terminal. When connecting an external power supply to terminal PC, however,
connect the shield of the power supply cable to the negative side of the external power supply. Do not directly earth
(ground) the shield to the enclosure, etc.
• Separate the wiring of the control circuit away from the wiring of the main circuit.
Make cuts in rubber bush of the converter unit side and lead the wires through.
+24 V
SD
Converter unit
External signal input using transistor
(sink logic)
PC
R
RDI, etc
+24 V
External signal input using transistor
(source logic)
RDI, etc
Converter unit
Micro signal contacts
Twin contacts
Rubber bush
(viewed from inside)
Make cuts along the lines on
the inside with a cutter knife
<Wiring example>