Electro-magnetic interference (EMI) and leakage currents
PRECAUTIONS FOR USE OF THE CONVERTER UNIT
61
3
Selecting the rated sensitivity current for the earth leakage circuit
breaker
When using the earth leakage circuit breaker with the inverter or the converter unit circuit, select its rated sensitivity current as
follows.
• Leakage currents of the inverter and the converter unit with a 6-phase transformer
400 V class (input power condition: 440 V/60 Hz, power supply unbalance within 3%)
• Leakage currents of the converter unit with a 12-phase transformer
• Breaker designed for harmonic and surge suppression
Rated sensitivity current
I
n
10
(Ig1 + Ign + Igi + Ig2 + Igm)
• Standard breaker
Rated sensitivity current
I
n
10
{Ig1 + Ign + Igi + 3
(Ig2 + Igm)}
Ig1, Ig2: Leakage currents in wire path during commercial
power supply operation
Ign:
Leakage current of inverter input side noise filter
Igm:
Leakage current of motor during commercial power
supply operation
Igi:
Leakage current of inverter unit
(When the converter unit is connected, add the
leakage current of converter unit.)
<Example>
• Selection example for the connection of the 400 V class
Item
Breaker designed
for harmonic and
surge suppression
Standard breaker
Leakage current Ig1 (mA)
1
66
5 m
= 0.11
3
1000 m
Leakage current Ign (mA)
0 (without noise filter)
Leakage current Igi (mA)
1 (without EMC filter)
For the leakage current of the inverter, refer to the
following table.
Leakage current Ig2 (mA)
1
66
60 m
= 1.32
3
1000 m
Motor leakage current Igm (mA)
0.36
Total leakage current (mA)
2.79
6.15
Rated sensitivity current (mA)
(
Ig
10)
30
100
Inverter/
converter unit
FR-A802-P
(Separated converter type)
Converter unit
FR-CC2-P
EMC filter
-
ON
OFF
2
70
2
1
2
1
(mA)
Motor capacity (kW)
For " " connection, the amount of leakage current is approx.1/3 of the above value.
(Three-phase three-wire delta
connection 400 V 60 Hz)
Example of leakage current per 1 km during
the commercial power supply operation
when the CV cable is routed in metal conduit
Leakage current example of three-
phase induction motor during the
commercial power supply operation
(Totally-enclosed fan-cooled
type motor 400 V 60 Hz)
0
2 0
4 0
6 0
8 0
100
120
leakage currents (mA)
leakage currents (mA)
2 3.5
5.5
8 1422
30
38
60
80
100
150
Cable size (mm
2
)
0. 1
0. 2
0. 3
0. 5
0. 7
1. 0
2. 0
1. 5 3. 7
2. 2
7. 5 1522
11
37
30
55
45
5.5
18. 5
Inverter
Noise
filter
ELB
Ig1
Ign
Igi
Ig2
Igm
M
5.5 mm
2
5 m
5.5 mm
2
60 m
400 V
2.2 kW
φ
3
Phase
earthing
(grounding)
Earthed-neutral