(N) Operation via communication and its settings
130
Converter status monitor
The signal within parentheses ( ) is the initial status. The description changes depending on the setting of
Pr.190 to Pr.195 (Output terminal
function selection)
.
Item
Instruction
code
Bit
length
Description
Example
Converter
status
monitor
H7A
8 bits
b0: RDB (inverter operation
enable signal (NC contact))
b1: Fixed to 0
b2: Fixed to 0
b3: RDA (inverter operation
enable signal (NO contact))
b4: RSO (inverter reset signal)
b5: IPF (instantaneous power
failure/undervoltage)
b6: FAN (fan fault signal)
b7: ABC1 (Fault)
Converter
status
monitor
(extended)
H79
16 bits
b0: RDB (inverter operation
enable signal (NC contact))
b1: Fixed to 0
b2: Fixed to 0
b3: RDA (inverter operation
enable signal (NO contact))
b4: RSO (inverter reset signal)
b5: IPF (instantaneous power
failure/undervoltage)
b6: FAN (fan fault signal)
b7: ABC1 (Fault)
b8 to b14: —
b15: Fault occurrence
0
0
0
0
0
0
0
1
b7
b0
[Example 1] H01...Inverter operation enable signal (NC contact) ON
[Example 2] H80...Fault occurrence
1
0
0
0
0
0
0
0
b7
b0
0
0
0
0
0
0
0
1
b0
0
0
0
0
0
0
0
0
b15
[Example 1] H0001...Inverter operation enable signal (NC contact) ON
1
0
0
0
0
0
0
0
b0
1
0
0
0
0
0
0
0
b15
[Example 2] H8080...Fault occurrence