175
Rated specifications per converter unit
The following table shows the rated specifications per converter unit. (For the rated specifications for operating two or three
units in parallel, refer to
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty,
allow time for the converter unit and the inverter to return to or below the temperatures under 100% load.
The converter unit output voltage varies according to the input power supply voltage and the load. The maximum point of the voltage waveform
at the converter unit output side is approximately the power supply voltage multiplied by
.
The power supply capacity is the value when at the rated output current. It varies by the impedance at the power supply side (including those of
the input reactor and cables).
The permissible voltage imbalance ratio is 3% or less. (Imbalance ratio = (highest voltage between lines - average voltage between three lines )
/ average voltage between three lines
100)
Model FR-CC2-H[]-P
400K
450K
500K
560K
Applicable motor capacity (kW)
320
360
400
450
Output
Overload current rating
150% 60 s, 200% 3 s
Rated voltage
430 to 780 VDC
Pow
er supply
Rated input current (A)
616
692.8
769.6
875.2
Rated input AC voltage/frequency
Three-phase 380 to 500 V 50/60 Hz
Permissible AC voltage fluctuation
Three-phase 323 to 550 V 50/60 Hz
Permissible frequency fluctuation
5%
Power supply capacity (kVA)
470
528
586
667
Protective structure (IEC 60529)
Open type (IP00)
Approx. mass (kg)
282
285
288
293