PARAMETER LIST
2 PARAMETER LIST
Set the necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be
made from the operation panel (FR-DU07). For the parameters not described in this Instruction Manual, refer to
the Instruction
Manual of FR-A700 series
.
REMARKS
• The shaded parameters in the table allow their settings to be changed during operation even if "0" (initial value) is set in
Pr. 77 Parameter
write selection
.
• Refer to the
page 76
for instruction codes for communication and availability of parameter clear, all clear, and parameter copy of each
parameter.
Parameter
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting
0
Torque boost
0 to 30%
0.1%
6/4/3/2/1%
—
1
Maximum frequency
0 to 120Hz
0.01Hz
120/60Hz
—
2
Minimum frequency
0 to 120Hz
0.01Hz
0Hz
—
3
Base frequency
0 to 400Hz
0.01Hz
60Hz
—
4
Multi-speed setting (high speed)
0 to 400Hz
0.01Hz
60Hz
—
5
Multi-speed setting (middle speed)
0 to 400Hz
0.01Hz
30Hz
—
6
Multi-speed setting (low speed)
0 to 400Hz
0.01Hz
10Hz
—
7
Acceleration time
0 to 3600/360s
0.1/0.01s
5/15s
—
8
Deceleration time
0 to 3600/360s
0.1/0.01s
5/15s
—
9
Electronic thermal O/L relay
0 to 500/0 to 3600A
0.01/0.1A
Rated
inverter
current
—
10
DC injection brake operation frequency
0 to 120Hz, 9999
0.01Hz
3Hz
—
11
DC injection brake operation time
0 to 10s, 8888
0.1s
0.5s
—
12
DC injection brake operation voltage
0 to 30%
0.1%
4/2/1%
—
13
Starting frequency
0 to 60Hz
0.01Hz
0.5Hz
—
14
Load pattern selection
0 to 5
1
0
—
15
Jog frequency
0 to 400Hz
0.01Hz
5Hz
—
16
Jog acceleration/deceleration time
0 to 3600/360s
0.1/0.01s
0.5s
—
17
MRS input selection
0, 2, 4
1
0
—
18
High speed maximum frequency
120 to 400Hz
0.01Hz
120/60Hz
—
19
Base frequency voltage
0 to 1000V, 8888, 9999
0.1V
9999
—
20
Acceleration/deceleration reference
frequency
1 to 400Hz
0.01Hz
60Hz
—
21
Acceleration/deceleration time
increments
0, 1
1
0
—
22
Stall prevention operation level
0 to 400%
0.1%
150%
—
23
Stall prevention operation level
compensation factor at double speed
0 to 200%, 9999
0.1%
9999
—
24 to 27
Multi-speed setting (4 speed to 7
speed)
0 to 400Hz, 9999
0.01Hz
9999
—
28
Multi-speed input compensation
selection
0, 1
1
0
—
29
Acceleration/deceleration pattern
selection
0 to 5
1
0
—
30
Regenerative function selection
0, 1, 2, 10, 11, 20, 21
1
0
—
31
Frequency jump 1A
0 to 400Hz, 9999
0.01Hz
9999
—
32
Frequency jump 1B
0 to 400Hz, 9999
0.01Hz
9999
—
33
Frequency jump 2A
0 to 400Hz, 9999
0.01Hz
9999
—
34
Frequency jump 2B
0 to 400Hz, 9999
0.01Hz
9999
—
35
Frequency jump 3A
0 to 400Hz, 9999
0.01Hz
9999
—
36
Frequency jump 3B
0 to 400Hz, 9999
0.01Hz
9999
—
37
Speed display
0, 1 to 9998
1
0
—
41
Up-to-frequency sensitivity
0 to 100%
0.1%
10%
—
42
Output frequency detection
0 to 400Hz
0.01Hz
6Hz
—