3
PARAMETER LIST
43
Output frequency detection for reverse
rotation
0 to 400Hz, 9999
0.01Hz
9999
—
44
Second acceleration/deceleration time
0 to 3600/360s
0.1/0.01s
5s
—
45
Second deceleration time
0 to 3600/360s, 9999
0.1/0.01s
9999
—
46
Second torque boost
0 to 30%, 9999
0.1%
9999
—
47
Second V/F (base frequency)
0 to 400Hz, 9999
0.01Hz
9999
—
48
Second stall prevention operation
current
0 to 220%
0.1%
150%
—
49
Second stall prevention operation
frequency
0 to 400Hz, 9999
0.01Hz
0Hz
—
50
Second output frequency detection
0 to 400Hz
0.01Hz
30Hz
—
51
Second electronic thermal O/L relay
0 to 500A, 9999/
0 to 3600A, 9999
0.01/0.1A
9999
—
52
DU/PU main display data selection
0, 5 to 14, 17, 18, 20, 21,
23 to 27, 32 to 35, 39 to 46,
52 to 57, 62 to 65, 100
1
0
54
FM terminal function selection
1 to 3, 5 to 14, 17, 18, 21,
24, 32 to 34, 39 to 44, 46
1
1
55
Frequency monitoring reference
0 to 400Hz
0.01Hz
60Hz
—
56
Current monitoring reference
0 to 500/0 to 3600A
0.01/0.1A
Rated
inverter
current
—
57
Restart coasting time
0, 0.1 to 5s, 9999/
0, 0.1 to 30s, 9999
0.1s
9999
—
58
Restart cushion time
0 to 60s
0.1s
1s
—
59
Remote function selection
0, 1, 2, 3
1
0
—
60
Energy saving control selection
0, 4
1
0
—
61
Reference current
0 to 500A, 9999/
0 to 3600A, 9999
0.01/0.1A
9999
—
62
Reference value at acceleration
0 to 220%, 9999
0.1%
9999
—
63
Reference value at deceleration
0 to 220%, 9999
0.1%
9999
—
64
Starting frequency for elevator mode
0 to 10Hz, 9999
0.01Hz
9999
—
65
Retry selection
0 to 5
1
0
—
66
Stall prevention operation reduction
starting frequency
0 to 400Hz
0.01Hz
60Hz
—
67
Number of retries at fault occurrence
0 to 10, 101 to 110
1
0
—
68
Retry waiting time
0 to 10s
0.1s
1s
—
69
Retry count display erase
0
1
0
—
70
Special regenerative brake duty
0 to 30%/0 to 10%
0.1%
0%
—
71
Applied motor
0, 1, 3 to 8, 13 to 18, 20, 23,
24, 30, 33, 34, 40, 43, 44,
50, 53, 54
1
0
—
72
PWM frequency selection
0 to 15/0 to 6, 25
1
2
—
73
Analog input selection
0 to 7, 10 to 17
1
1
—
74
Input filter time constant
0 to 8
1
1
—
75
Reset selection/disconnected PU
detection/PU stop selection
0 to 3, 14 to 17
1
14
—
76
Fault code output selection
0, 1, 2
1
0
—
77
Parameter write selection
0, 1, 2
1
0
—
78
Reverse rotation prevention selection
0, 1, 2
1
0
—
79
Operation mode selection
0, 1, 2, 3, 4, 6, 7
1
0
—
80
Motor capacity
0.4 to 55kW, 9999/
0 to 3600kW, 9999
0.01/0.1kW
9999
—
81
Number of motor poles
2, 4, 6, 8, 10, 12, 14, 16, 18,
20, 9999
1
9999
—
82
Motor excitation current
0 to 500A, 9999/
0 to 3600A, 9999
0.01/0.1A
9999
—
83
Rated motor voltage
0 to 1000V
0.1V
200/400V
—
84
Rated motor frequency
10 to 120Hz
0.01Hz
60Hz
—
Parameter
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting