OCH790 _41
1500 (U7): Superheat due to low discharge temperature trouble
Chart 2 of 2
Diagnosis of failure
*For the voltage, refer to "How to check the components".
Replace the indoor LEV.
Continued from the previous page.
Replace the indoor controller board.
Replace the 63HS.
Replace the outdoor multi controller circuit
board.
Check the voltage and appearance of the indoor
controller board.
Check the 63HS voltage.
Is the resistance detected?
Is the voltage normal?
Is it free from any trace of overheating
or burning?
Is the voltage(*) detected?
No
No
No
Yes
Yes
Yes