OCH790 _90
8-7. How to check the parts
8-7-1. Checkpoints for each part
■
Thermistors
Disconnect the connector then measure the resistance with a multimeter (at the ambient temperature 10 to 30°C [50 to
80°F]).
Thermistors
Normal
Abnormal
TH4 (Compressor)
160 to 410 kΩ
Open or short
TH2 (HIC pipe)
4.3 to 9.6 kΩ
TH3 (Outdoor liquid pipe)
TH6 (Suction pipe)
TH7 (Ambient)
TH8 (Heat sink)*
39 to 105 kΩ
*
TH8 is internal thermistor of power module. (V)
■
Fan motor (MF1, MF2)
Red
Blue
Brown
Orange
White
M
1
2
3
4
5
6
7
Measure the resistance between the connector pins with a multimeter (at the ambient temperature 20°C [68°F]).
Connector pins
Normal
Abnormal
Red - Blue
1.1 ± 0.05 MΩ
Open or short
(Short, for White - Blue)
Brown - Blue
40 ± 4 kΩ
Orange - Blue
220 ± 22 kΩ
White - Blue
Open
■
Solenoid valve coil <4-way valve> (21S4)
Measure the resistance between the terminals with a multimeter (at the ambient temperature 20°C [68°F]).
Normal
Abnormal
2085 ± 208.5 Ω
Open or short
■
Motor for compressor (MC)
W
V
U
Measure the resistance between the terminals with a multimeter (at the ambient temperature 20°C [68°F]).
Model
Normal
Abnormal
PUMY-P•VKM
0.305 ± 0.015 Ω
Open or short
PUMY-P•YKM
0.466 ± 0.023 Ω
■
Solenoid valve coil <Bypass valve> (SV1)
Measure the resistance between the terminals with a multimeter (at the ambient temperature 20°C [68°F]).
Normal
Abnormal
1182.5 ± 83 Ω
Open or short
■
Linear expansion valve (LEV-A)
1
2
3
4
5
M
Gray
Orange
Red
Yellow
Black
Connector pins
Normal
Abnormal
Gray - Black
46 ± 3 Ω
Open or short
Gray - Red
Gray - Yellow
Gray - Orange
■
Linear expansion valve (LEV-B)
1
2
3
4
5
M
Red
Blue
Orange
Yellow
White
Connector pins
Normal
Abnormal
Red - White
46 ± 4 Ω
Open or short
Red - Orange
Red - Yellow
Red - Blue