OCH790 _118
Photo 13
Valve bed
Compressor
(MC)
Valve bed
fixing screw
Valve
bed
fixing
screws
Compressor
fixing nuts
Separator
Accumulator
Figure 2
Separator
fixing
screws
Separator
fixing screw
14. Removing the accumulator
1. Remove the service panel. (See Photo 1)
2.
Remove the top panel. (See Photo 1)
3.
Remove 2 cover panel (front) fixing screws (5 × 12) and remove the cover panel (front). (See Photo 4)
4. Remove 4 cover panel (rear) fixing screws (5 × 12) and remove the cover panel (rear).
5. Remove the electrical parts box. (See Photo 5)
6.
Remove 3 valve bed fixing screws (4 × 10) and 4 ball valve and stop valve fixing screws (5 ×16) , and then remove
the valve bed. (See Photo 4 and 7)
7.
Remove 3 side panel (R) fixing screw (5 × 12) in the rear of the unit and then remove the side panel (R).
8. Recover refrigerant.
9.
Remove 4 welded pipes of accumulator inlet and outlet.
10. Remove 2 accumulator leg fixing screws (4 × 10).
Note:
•
Recover refrigerant without spreading it in the air.
Photo 14
Accumulator
Inlet
Outlet
Photo 15
Accumulator
Accumulator
leg
Accumulator leg fixing
screws