OCH790 _10
3-4.
System Specifications
3-4-1. Outdoor Unit
Outdoor unit
Model name
P112
P125
P140
Capacity
Cooling (kW)
12.5
14.0
15.5
Heating (kW)
14.0
16.0
18.0
Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling
Indoor:
D.B. 27°C/W.B. 19°C
Outdoor: D.B. 35°C
Heating
Indoor:
D.B. 20°C
Outdoor: D.B. 7°C/W.B. 6°C
3-4-2. Method for identifying MULTI-S model
■
Outdoor unit <When using model 125>
PU M Y
─
P 125 Y K M
─
BS
Outdoor
unit
Refrigerant R410A
MULTI-S
Frequency conversion
controller
Indicates equivalent to
Cooling
capacity(kcal/
h)
Power
supply
V
:
1-phase
220-230-240
V,
50
Hz
220-230
V,
60
Hz
Y
:
3-phase
380-400-415
V,
50
Hz
380
V,
60
Hz
Outdoor
unit model
type
M-NET control
Sub number
Salt
proof type
5
3-4-3. Operating temperature range
Cooling
Heating
Indoor intake air temperature
W.B. 15 to 24°C
D.B. 15 to 27°C
Outdoor intake air temperature
D.B. −5 to 52°C
*
1
W.B. −20 to 15°C
D.B.: Dry Bulb Temperature
W.B.: Wet Bulb Temperature
*1. 10 to 52°C D.B.: When connecting PKFY-P10/15/20/25/32VLM, PFFY-P20/25/32VKM, PFFY-P20/25/32VCM,
PFFY-P20/25/32VLEM, PFFY-P20/25/32VLRM(M), and M series, S series, and P series type indoor
unit.
■
When connecting fresh air type indoor unit
PEFY-P·VMHS-E-F
Cooling
Heating
Indoor and outdoor
intake air temperature
D.B. 17 to 43°C
*2
W.B. 15.5 to 35°C
D.B. -5 to 20°C
*3
*2.
Thermo-OFF (FAN-mode) automatically starts if the outdoor temp. is lower than 17°C D.B.
*3.
Thermo-OFF (FAN-mode) automatically starts if the outdoor temp. is higher than 21°C D.B.
■
When connecting PWFY unit
Cooling
Heating
Indoor intake water temperature
—
*4
D.B. 10 to 45°C
Outdoor intake air temperature
—
*4
W.B. -20 to 15°C
*4. PWFY series can operate in Heating mode but not in Cooling mode. An indoor unit other than that of PWFY series
can operate in Cooling mode.
A PWFY series and other series cannot operate simultaneously.
The operation of PWFY series takes precedence over other series. While a PWFY series is operating, other series
do not operate.
The set temperature on the remote controller represents the target temperature of the outlet water.
■
When connecting Cylinder Unit or Hydrobox
Cooling
DHW only
ATW Heating only
DHW + ATA
Heating
*5
ATW H ATA
Heating
*5
Outlet water temperature
—
*6
55°C Max.
55°C Max.
55°C Max.
45 to 55°C Max.
Outdoor temperature
—
*6
−20 to 35°C
−20 to 21°C
7 to 35°C
−10 to 35°C
*7
*5. ATA unit: Air to Air unit (other than PWFY, Cylinder Unit or Hydrobox)
*6.
Cylinder Unit and Hydrobox cannot operate Cooling mode in connecting PUMY.
*7.
When outdoor temp. is less than 7°C, outlet water temp. is lowered. (Refer to the figure below "Temperature curve of
max. outlet water".)
Furthermore, outlet air temperature is lowered.